Newly redesigned MSCT Series »

Sensors DT2630 (Temp For Duct)

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

Wireless, Temp, Duct, 4"

Application

  • Museums
  • Churches
  • Historical Buildings & New Construction

Product specifications

Input Voltage:
Battery; 1 (Duracell DL123A), Lithium 3V 1400mAh 45 mA maximum
Battery Life:
2-3 years typical
Operating Temperature Range:
14 to 140ºF (-10 to 60ºC)
Operating RH Range:
5 to 65%, Non-condensing
Storage Temperature Range:
Temperature: 0 to 176ºF (-17 to 80ºC) | Humidity: 5 to 65%, Non-condensing
Sensor Operating Temperature Range:
-40 to 200ºF (-40 to 93ºC)
Accuracy:
+/- 1ºF (+/- 0.555ºC) 12 bit resolution
Probe Material:
304 Stainless Steel
Probe Diameter:
0.25” (6.35 mm)
Probe Length:
4”, 6”, 8”, 12” & 18”
Fitting Material | Flammability Rating:
ST801A Polyamide 66 Plastic (PA66) toughened “Zytel”, UL94-HB
Data Protocol:
IEEE 802.15.4-2003/2006
RF Characteristics:
900 MHz, Operating Frequency 10 channels between 902 – 928 MHz Transmitter Power: 11 dBm | Receiver Sensitivity: -11 dBm
Data Transmission:
75 seconds (default) | 300 seconds (optional)
Transmission Distance:
200 – 300 ft horizontally depending on building type and construction, and typically one floor above and below the transceiver vertically
Enclosure Material | Flammability Rating:
Standard: ABS Plastic | UL94 NEMA 4X: Polycarbonate Plastic | UL94-HB
Product Dimensions:
Standard: (L) 5.77” (146.56 mm) x (W) 3.19” (81.03 mm) x (H) 1.88” (47.75 mm) NEMA 4X: (L) 4.52” (114.81 mm) x (W) 3.54” (89.92 mm) x (H) 2.16” (54.86 mm)
Product Weight:
DT2630A-04: 0.99 lbs (0.45 kg) DT2630AE-04: 2.82 lbs (1.28 kg) DT2630A-06: 1.00 lbs (0.45 kg) DT2630AE-06: 2.83 lbs (1.28 kg) DT2630A-08: 1.01 lbs (0.46 kg) DT2630AE-08: 2.84 lbs (1.29 kg) DT2630A-12: 1.03 lbs (0.47 kg) DT2630AE-12: 2.86 lbs (1.30 kg) DT2630A-18: 1.05 lbs (0.48 kg) DT2630AE-18: 2.88 lbs (1.31 kg)

Related products