This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
DISCONTINUED NO DIRECT REPLACEMENT - Wireless, Wireless Temp, Outdoor, NEMA 4X Enclosure
Application
- Museums
- Churches
- Historical Buildings & New Construction
Product specifications
Input Voltage:
Battery; 1 (Duracell DL123A), Lithium 3V 1400 mAh 45 mA maximum
Operating Temperature Range:
14 to 140ºF (-10 to 60ºC)
Operating Humidity Range:
5 to 65%, Non-condensing
Storage Temperature Range:
Temperature: 0 to 176ºF (-17 to 80ºC) | Humidity: 5 to 65%, Non-condensing
Sensor Operating Temperature Range:
40 to 200ºF (-40 to 93ºC)
Accuracy:
+/- 1ºF (+/- 0.555ºC) 12 bit resolution
Probe Material:
304 Stainless Steel
Probe Diameter:
0.250” (6.35 mm)
Probe Length:
3.25” (82.55 mm)
Fitting Material:
Polyamide 6 plastic; flammability rating UL94 V-2
Data Protocol:
IEEE 802.15.4-2003/2006
RF Characteristics:
900 MHz, Operating Frequency 10 channels between 902 – 928 MHz
Transmitter Power: 11 dBm | Receiver Sensitivity: -11 dBm
Data Transmission:
75 seconds (default) | 300 seconds (optional)
Transmission Distance:
200 – 300 ft horizontally depending on building type and construction, and typically one floor
above and below the transceiver vertically
Enclosure Material | Flammability Rating:
Polycarbonate Plastic | UL94-HB
Product Dimensions:
(L) 4.52” (114.81 mm) x (W) 2.55” (64.77 mm) x (H) 2.16” (54.86 mm)
Product Weight:
0.80 lbs (0.36 kg)