This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
DISCONTINUED NO DIRECT REPLACEMENT - Wireless, Signal Repeater, 24VAC
Application
- Museums
- Churches
- Historical Buildings & New Construction
Product specifications
Supply Voltage:
24 VAC, 60 Hz (full wave rectified)
Supply Current:
300 mA
Connections:
Screw Terminal Blocks
Wire Size:
16 AWG (1.31 mm²) to 26 AWG (0.129 mm²)
Terminal Block Torque Rating:
0.37 ft-lb (0.5 Nm) Nominal
Operating Temperature Range:
14 to 140ºF (-10 to 60ºC)
Operating Humidity Range:
30 to 50% RH, Noncondensing
Storage Temperature Range:
-4 to 176ºF (-20 to 80ºC), 70% RH
Data Protocol:
IEEE 802.15.4-2003/2006
RF Characteristics:
900 MHz, Operating Frequency 10 channels between 902 – 928 MHz
Transmitter Power: 11 dBm | Receiver Sensitivity: -11 dBm
Transmission Distance:
200 – 300 ft horizontally depending on building type and constructions, and typically one floor above and below the transceiver vertically
Network Addressable:
1 to 64, Dip switch selectable | All switches set to OFF = Address 1 (default) Address of repeater must match the Network ID of the receiver/transceiver
Enclosure Material | Flammability Rating:
Standard: ABS Plastic | UL94-5VA | NEMA 4X: Polycarbonate Plastic | UL94 HB
Product Dimensions:
Standard: (L) 7.28” (184.91 mm) x (W) 4.72” (119.89 mm) x (H) 2.36“ (59.94 mm)
NEMA 4X: (L) 6.73” (170.94 mm) x (W) 4.76” (120.90 mm) x (H) 2.16” (54.86 mm)
Product Weight:
Standard: 1.65 lbs (0.75 kg) | NEMA 4X: 1.675 lbs (0.76 kg)