This product is covered by ACI's Five (5) Year Limited Warranty. Learn more
Product overview
Split Core, N/O ECM Current Switch, Current Sensing Range: 0–25 A, Trip Adjustment Range: 0.075–0.5 A
Application
- On/Off “Status” Indication
- Pumps
- Compressors
- Process Control
- Industrial Equipment
- OEM Opportunities
- Fans
- Fan Wall
- Appliances
Product specifications
Monitored Current Type:
AC Current
Maximum AC Voltage:
600 VAC
Operating Frequency Range:
50/60 Hz
Core Style:
Split-Core
Sensor Power:
Induced from the Monitored Conductor (Use Insulated Conductors only)
Amperage Range:
0 to 25 A
Isolation Voltage:
600 VAC
Trip Point Style | Adjustable Trip Point Range:
Adjustable Trip Point | 0.075 A to 0.50 A
Hysteresis:
10% of Trip Level Current, Typical
Contact Type:
Normally-Open “N/O”
“Status” Contact Rating:
100 mA Continuous @ 30 VAC/VDC
Contact “On” Resistance | “Off” Resistance:
< 10 Ohms (when tripped) | > 1 Meg Ohms (Open)
Response Time:
< 5 Seconds Typical
Aperture Size (Diameter) | Wire Size:
0.20”(5.0mm) x 0.49”(12.5mm) | Fits 10 AWG to 14 AWG THHN Insulated Wire
DIN Rail Mounting:
35 mm
Operating Temperature Range:
32°F to 140°F (0°C to 60°C)
Operating RH Range:
10 to 90%, non-condensing
Storage Temperature | RH Range:
-40 to 158°F (-40 to 70°C) | 10% to 90% RH, non-condensing
Enclosure Material | Flammability Rating:
PC/ABS (Polycarbonate/ABS Blend) | UL94-V0
Wiring Connections / Wire Size:
2 Position Screw Terminal Block (Not Polarity Sensitive) | 16 to 22 AWG (1.31 mm2 to 0.33 mm2) Copper Wires Only
Terminal Block Torque Rating:
4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)
Minimum Mounting Distance:
1” (2.6 cm) between current switch & other magnetic devices (Relays, Contactors, Transformers)
Agency Approvals:
UL/CUL US Listed (UL 916) Energy Management Equipment (File # E334792), CE, UKCA, RoHS, WEEE, CAN ICES-3 / NMB-3
Product Weight:
0.14 lbs. (0.065 kg)
Product Dimensions:
1.93" (48.99 mm) x 1.31" (33.17 mm) x 2.18" (55.37 mm)

