Thermistors Freezer

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

10,000 Ohm Thermistor (Type II), 2" Freezer Probe 316SS, 30'

Application

  • Roof Top Units
  • Mixed Air/Discharge/Supply/Return Air Temperature Monitoring
  • Data Centers
  • Hospitals

Product specifications

Sensor Type | Sensor Curve:
Thermistor | Non-Linear, NTC (Negative Temperature Coefficient)
Number Sensing Points:
One
Number Wires:
Three Conductors (White and Two Red Wires); Polarity Sensitive (Tie Red wires together)
Sensor Output @ 25ºC (77ºF):
A/CP (Type II): 10KΩ nominal | A/AN (Type III): 10KΩ nominal
Accuracy 0-70ºC (32-158ºF):
A/CP Series & A/AN Series: +/- 0.85ºC (+/-1.53ºF)
Stability:
Sensor Dependent; Contact ACI for more information on specific sensor
Power Dissipation Constant:
A/CP-Series & A/AN Series: 2 mW/ºC
Sensor Operating Temperature Range:
-40 to 150ºC (-40 to 302ºF)
Enclosure Rating:
-40 to 70ºC (-40 to 158ºF)
Storage Temperature Range:
-40 to 80ºC (-40 to 176ºF)
Operating Humidity Range:
10 to 95% RH, non-condensing
Enclosure Material | Flammability Rating:
Polystyrene | UL94-V2
Enclosure Rating:
NEMA 4X (IP 66)
Cable Gland (Fitting) Size | Hole Size | Material:
PG7 | 15 mm (0.591”) | Polyamide 6
Cable Gland Sleeve Material | Wire Clamping Size:
0.098” (2.5 mm) to 0.256” (6.5 mm) | IP 68 (NEMA 6P)
Cable Gland IP Rating | Torque Rating:
2.5 Nm (22.127 lb. inch)
Probe Material:
316 Stainless Steel
Probe Length:
2” (50.8 mm)
Probe Diameter:
0.1875” (4.76 mm)
Lead Length | Conductor Size:
2” (50.8 mm) | 0.1875” (4.76 mm)
Lead Length | Conductor Size:
30’ (9.15 m) | 0.106” nominal (2.69 mm)
Conductor Size | Conductor Material:
24 AWG (0.51 mm) | Silver Plated Copper
Lead Wire Insulation | Jacket Color:
FEP/FEP (Teflon) Jacketed Cable | White
Product Weight:
A/xxK-FRZ2”-30’: 0.36 lbs. (0.163 kg) | A/xxK-FRZ2”-4X-30’: 0.60 lbs. (0.272 kg)
Agency Approvals:
WEEE, RoHS2

Related products

Glycol Kit
Item: 147221

Model: A/TB-2.0-GLY

Thermal Buffer, 2 oz Nalgene Bottle, 1 Sensing Point, Mounting Bracket, Food Grade Glycol, Rated to -40C, Probe Size accepted: 0.098” to 0.256” (2.49mm to 6.50mm)

$63.00