This product is covered by ACI's Five (5) Year Limited Warranty. Learn more
Product overview
100 Ohm RTD, 2" Freezer Probe 316SS, 10', NIST Cert
Application
- Roof Top Units
- Discharge Air/Supply/Return/Mixed Air Duct Temperature
- Remote Temperature Sensing
- Hydronic Systems
Product specifications
Sensor Type | Sensor Curve:
Platinum RTD | Linear, PTC (Positive Temperature Coefficient)
Number Sensing Points:
One
Number Wires:
Three Conductors (White and Two Red Wires); Polarity Sensitive (Tie Red wires together)
Sensor Output @ 0ºC (32ºF):
A/100-LTS Series: 100 Ohms nominal | A/1K-LTS Series: 1000 Ohms nominal
Platinum RTD Tolerance Class:
Class B Accuracy Formula: +/- ºC = (+/- 0.30ºC + (0.005 x |t|)) where t is the Absolute Value of temperature in ºC above or below 0ºC
-200ºC (-328ºF): +/- 1.30ºC (+/- 2.34ºF) | 0ºC (-32ºF): +/- 0.30ºC (+/- 0.54ºF)
Din Standard | Temperature Coeffcient:
3850 ppm / ºC | DIN EN 60751 (IEC 751)
Platinum RTD Response Time (63% Step Change):
A/100-LTS Series: In still air: 3:40 (Min:Sec) In water: 19 (Sec)
A/1K-LTS Series: In still air: 3:50 (Min:Sec) In water: 22 (Sec)
Sensor Operating Temperature Range:
-198 to 150ºC (-324 to 302ºF)
Enclosure Temperature Rating:
“-GD” Enclosure: -40 to 100ºC (-40 to 212ºF)
“-4X” Enclosure: -40 to 70ºC (-40 to 158ºF)
Storage Temperature Range:
-40 to 80ºC (-40 to 176ºF)
Operating Humidity Range:
10 to 100% RH
Enclosure Material | Flammability Rating:
“-GD” Enclosure: Galvanized Steel | “-4X” Enclosure: Polystyrene | UL94-V2
NEMA Rating:
“-GD” Enclosure: NEMA 1 (IP10) | “-4X” Enclosure: NEMA 4X (IP 66)
Cable Gland (Fitting) Size | Hole Size | Material:
PG7 | 15 mm (0.591”)
Cable Gland Sleeve Material | Wire Clamping Size:
Polyamide 6 | Neoprene
0.098” (2.5 mm) to 0.256” (6.5 mm) | IP 68 (NEMA 6P)
Cable Gland IP Rating | Torque Rating:
2.5 Nm (22.127 lb. inch)
Probe Material | Length | Diameter:
316 Stainless Steel | 2” (50.8 mm) | 0.1875” (4.76 mm) nominal
Lead Length | Conductor Size:
10’ (3.05 m) or 30’ (9.15 m) | 0.106” nominal (2.69 mm)
Conductor Size | Conductor Material:
24 AWG (0.51 mm) | Silver Plated Copper
Lead Wire Insulation | Jacket Color:
FEP/FEP (Teflon) Jacketed Cable | White
Product Weight:
A/xx-LTS-10’: 0.16lbs (0.073kg) | A/xx-LTS-4X-10’: 0.40lbs (0.181kg)
A/xx-LTS-GD-10’: 0.71lbs (0.322kg) | A/xx-LTS-30’: 0.36lbs (0.163kg)
A/xx-LTS-4X-30’: 0.60lbs (0.272kg) | A/xx-LTS-GD-30’: 0.91lbs (0.413kg)
Agency Approvals:
CE, UKCA, WEEE, RoHS
: