This product is covered by ACI's Five (5) Year Limited Warranty. Learn more
Product overview
1,000 Ohm Nickel RTD, Duct, 12", Plastic Enclosure
Application
- Roof Top Units
- Supply/Discharge/Return/Mixed Air Temperatures
Product specifications
Sensor Type:
Nickel RTD
Sensor Curve:
PTC (Positive Temperature Coefficient)
Number Sensing Points:
One
Number Wires:
Two (Non-Polarity Sensitive)
Sensor Output @ 21.1ºC (70ºF):
1000 Ohms nominal
Lead Wire Colors:
Red/Red
Sensor Accuracy:
-40ºC (-40ºF): +/- 1.52ºC (+/- 2.73ºF)
0ºC (32ºF): +/- 0.4ºC (+/- 0.72ºF)
21.1ºC (70ºF): +/- 0.17ºC (+/- 0.34ºF))
54.4ºC (130ºF): +/- 0.56ºC (1.00ºF)
121ºC (250ºF): +/- 1.25ºC (+/- 2.25ºF)
Din Standard | Temperature Coeffcient:
Din 43760 | 6370 ppm/ºC
Stability:
8 Seconds nominal
Response Time (63% Step Change):
+/- 0.05% after 1000 Hours @ 150ºC (302ºF)
Self-Heating | Maximum Operating Current:
0.3ºC/mW (Still Air) | 5 mA
Storage Temperature Range:
-40 to 85ºC (-40 to 185ºF)
Operating Temperature Range:
-40 to 250ºF (-40 to 121ºC)
Operating Humidity Range:
10 to 95% RH, non-condensing
Probe Material:
304 Stainless Steel
Fitting Material | Flammability Rating:
Polyamide 66 (High Performance Nylon) | UL94-HB
Foam Pad Material | Flammability Rating:
Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
Lead Length | Conductor Size:
4”, 6” & 8” Sensors: 14” (35.6cm) | 22 AWG (0.65mm)
12”or 18” Sensors: 24” (61cm) | 22 AWG (0.65mm)
Lead Wire Insulation | Wire Rating:
Etched Teflon (PTFE) Colored Leads | Mil Spec 16878/4 Type E)
Conductor Material:
Silver Plated Copper
Probe Diameter:
0.250” (6.35mm)
Agency Approvals:
CE, RoHS2, WEEE