This product is covered by ACI's Five (5) Year Limited Warranty. Learn more
Product overview
High Accuracy 10,000 Ohm Thermistor (Type III), Duct, 6", Plastic Enclosure, NIST Cert
Application
- Roof Top Units
- Supply/Discharge/Return/Mixed Air Temperatures
Product specifications
Sensor Type:
Thermistor
Sensor Curve:
Non-Linear, NTC (Negative Temperature Coefficient)
Number Sensing Points:
One
Sensor Output @ 21.1ºC (70ºF):
A/0.1AN Series: 2 mW/ºC nominal
A/0.1CP Series: 1 mW/ºC nominal
Stability:
A/0.1AN Series (5 Years): +/- 0.127ºC (0.228ºF) @ 100ºC (212ºF)
A/0.1CP Series (5 Years): +/- 0.12ºC (0.216ºF) @ 25ºC (77ºF) (10 Years): +/- 0.60ºC (1.08ºF) @ 25ºC (77ºF)
Response Time (63% Step Change):
10 Seconds nominal
Operating Temperature Range:
0 to 70ºC (32 to 158ºF)
Storage Temperature Range:
0 to 70ºC (32 to 158ºF)
Operating Humidity Range:
10 to 95% RH, non-condensing
NIST Certification:
3 Point NIST Certificate available
Probe Material:
304 Stainless Steel
Probe Diameter:
0.250” (6.35mm)
Fitting Material | Flammability Rating:
Polyamide 66 (High Performance Nylon) | UL94-HB
Foam Pad Material | Flammability Rating:
Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
Lead Length | Conductor Size:
12” (30.5cm) | 22 AWG (0.65mm)
Lead Wire Insulation | Wire Rating:
Etched Teflon (PTFE) Colored Leads | Mil Spec 16878/4 Type E)
Conductor Material:
Silver Plated Copper
Agency Approvals:
CE, RoHS2, WEEE