This product is covered by ACI's Five (5) Year Limited Warranty. Learn more
Product overview
High Accuracy 10,000 Ohm Thermistor (Type III), Bullet Probe, 1"
Application
- Roof Top Units
- Discharge Air/Supply/Return/Mixed Air Duct Temperature
- Remote Temperature Sensing
Product specifications
Sensor Type:
Thermistor
Sensor Curve:
Non-Linear, NTC (Negative Temperature Coecient)
Number Sensing Points:
One
Number Wires:
Two (Non-Polarity Sensitive)
Sensor Output @ 25ºC (77ºF):
A/0.1AN Series (Type III): 10K nominal)
A/0.1CP Series (Type II): 10K nominal)
Lead Wire Colors:
A/0.1AN Series (Type III): (White/Black)
A/0.1CP Series (Type II): (Green/Gray)
Accuracy 0-70ºC (32-158ºF):
+/- 0.1ºC (+/- 0.18ºF)
For best accuracy and long term stability the sensor should be used in applications where the operating temperatures remain within the specied operating temperature range of 0 to 70ºC (32 to 158ºF)
Power Dissipation Constant:
A/0.1AN Series: 2 mW/ºC nominal
A/0.1CP Series: 1 mW/ºC nominal
Stability:
A/0.1AN Series (5 Years): +/- 0.127ºC (0.228ºF) @ 100ºC (212ºF)
A/0.1CP Series (5 Years): +/- 0.12ºC (0.216ºF) @ 25ºC (77ºF) (10 Years): +/- 0.60ºC (1.08ºF) @ 25ºC (77ºF)
The sensor will operate over an extended operating temperature range of -40 to 150ºC (-40 to 302ºF) without damaging the sensor but the accuracy and long term stability will not meet the specications above
Response Time (63% Step Change):
10 Seconds nominal
Probe Material:
304 Stainless Steel
Operating Temperature Range:
0 to 70ºC (32 to 158ºF)
Storage Temperature Range:
0 to 70ºC (32 to 158ºF)
: