Newly redesigned MSCT Series »

Thermistors Quick Connects

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

10,000 Ohm Thermistor (Type II), Duct, Without Box, 4", 120" Plenum Cable, Quick Connects

Application

  • Roof Top Units
  • Monitoring Supply/Discharge/Return/Mixed Air Temperatures

Product specifications

Sensor Type | Sensor Curve:
Thermistor | Non-Linear, NTC (Negative Temperature Coefficient)
Number Sensing Points:
One
Number Wires:
Two (Non-Polarity Sensitive)
Nominal Thermistor Resistive Output @ 77°F (25°C) (Lead Wire Colors):
A/1.8K: 1.8KΩ nominal | (Red/Yellow) A/3K: 3KΩ nominal A/AN (Type III): 10KΩ nominal A/AN-BC: 5.238KΩ nominal A/CP (Type II): 10KΩ nominal A/CSI: 10KΩ nominal A/10KS: 10KΩ nominal A/10K-E1: 10KΩ nominal A/20K: 20KΩ nominal A/100KS Series: 100KΩ nominal
Accuracy 0-70ºC (32-158ºF):
+/-0.2ºC (+/-0.36ºF) except A/10K-E1 Series: +/- 0.3ºC (+/-0.54ºF) A/1.8K Series: +/- 0.5ºC @ 25ºC (77ºF) and (+/-1.0ºC) (+/-1.8ºF)
Power Dissipation Constant:
3 mW/ºC except A/1.8K Series: 1 mW/ºC; A/10K-E1 Series: 2 mW/ºC
Response Time (63% Step Change):
10 Seconds nominal
Operating Temperature Range:
-40 to 115ºC (-40 to 239ºF)
Storage Temperature Range:
-40 to 85ºC (-40 to 185ºF)
Operating Humidity Range:
10 to 95% RH, non-condensing
Probe Material | Flange Material:
304 Stainless Steel | Galvanized Steel
Fitting Material | Flammability Rating:
Polyamide 66 (High Performance Nylon) | UL94-HB
Foam Pad Material | Flammability Rating:
Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
Lead Length | Conductor Size:
96” (8 ft (2.44m)); 120” (10 ft (3.05m)) or 240” ** (20 ft (6.10m)) | 22 AWG (0.65mm)
Lead Wire Insulation | Wire Rating:
FEP/FEP Teflon Jacketed Cable
Conductor Material:
Tin Plated Copper
Connections:
Two, ¼” Insulated Female Quick Connects (Amp® Part# 2-520264-2)
Probe Diameter:
0.250” (6.35mm)
Agency Approvals:
CE, RoHS, WEEE