RH Room Thermistor

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

Relative Humidity, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), Room (R2), ± 3% Accuracy, 10,000 Ohm Thermistor (Type III), Custom Logo, w/ Override

Application

  • Humidification
  • Dehumidification
  • Monitoring Indoor Space Humidity
  • Clean Rooms
  • Hospitals
  • Process Control
  • Laboratories
  • Museums
  • Schools
  • Office Buildings
  • Data Centers
  • ESD (Anti-Static) Control

Product specifications

Supply Voltage:
4-20 mA: 250 Ohm Load: 15 - 40 VDC / 18 - 28 VAC | 500 Ohm Load: 18 - 40 VDC / 18 - 28 VAC 0-5 VDC: 12 - 40 VDC / 18 - 28 VAC | 0-10 VDC: 18 - 40 VDC / 18 - 28 VAC Note: Reverse Polarity Protected
Supply Current:
Voltage Output: 8 mA maximum (0.32 VA) Current Output: 24 mA maximum (0.83 VA)
Output Load Resistance:
4-20 mA: 700 Ohms maximum 0-5 VDC or 0-10 VDC: 4K Ohms Minimum
Output Signals:
2-wire: 4 - 20 mA (Factory Default) 3-wire: 0-5 or 0-10 VDC & 4 - 20 mA (Field Selectable)
Accuracy @ 77°F (25°C):
Model Dependent: +/- 1% over 20% RH Range between 20 to 90% | +/- 2%, or 3% from 10 to 95%
RH Measurement Range:
0-100%
Operating RH Range:
0 to 95% RH, non-condensing
Operating Temperature Range:
35 to 122°F (1.5 to 60°C)
Storage Temperature Range:
-40 to 149°F (-40 to 65°C)
RH Stability | Repeatability | Sensitivity:
Less than 2% drift / 5 years | 0.5% RH | 0.1% RH
Response Time (63% Step Change):
20 Seconds Typical
RH Sensor Type:
Capacitive with Hydrophobic Filter
RH Transmitter Stabilization Time:
30 Minutes (Recommended time before doing accuracy verification)
Connections | Wire Size:
Screw Terminal Blocks (Polarity Sensitive) | 16 (1.31 mm²) to 26 AWG (0.129 mm²)
Terminal Block Torque Rating:
4.43 to 5.31 lb-in (0.5 to 0.6 Nm)
NIST Test Points:
Default Test Points: 3 Points (20%, 50% & 80%) 1% NIST Test Points: 5 Points within selected 20% Range (ie. 30%-50% are 30, 35, 40, 45 & 50)
Nominal Thermistor Resistive Output @ 77°F (25°C) (Lead Wire Colors):
RHx-1.8K Series: 1.8K (Red/Yellow) RHx-3K Series: 3K (White/Brown) RHx-AN Series (Type III): 10K (White/White) RHx-AN-BC Series: 5.238K (White/Yellow) RHx-CP Series (Type II): 10K (White/Green) RHx-CSI Series: 10K (Green/Yellow) RHx-10KS Series: 10K (White/Blue) RHx-10K-E1 Series: 10K (Gray/Orange) RHx-20K Series: 20K (Brown/Blue) RHx-50K Series: 50K nominal (Brown/Yellow) RHx-100KS Series: 100K (Black/Yellow)
Accuracy @ 77°F (25°C):
+/- 0.36°F (0.2°C) except 10K-E1 Series: +/- 0.54°F (0.3°C) 1.8K Series: +/- 0.9°F (0.5°C) @ 77°F (25°C) & +/- 1.8°F (1.0°C) from 32 to 158°F (0 to 70°C)
Power Dissipation Constant:
3 mW/°C except 1.8K Series: 1 mW/°C; 10K-E1 Series: 2 mW/°C
Response Time (63% Step Change):
10 Seconds nominal
Connections | Wire Size:
Screw Terminal Blocks | 16 (1.31 mm²) to 26 AWG (0.129 mm²)
Terminal Block Torque Rating:
4.43 to 5.31 lb-in (0.5 to 0.6 Nm)
Enclosure Material | Color:
“-R2” Enclosure: ABS (White) “-R” Enclosure: ABS (Beige)
Enclosure Flammability Rating:
UL94-HB
Product Dimensions:
“-R2” Enclosure: 4.50” (114.3 mm) x 2.75” (69.85 mm) x 1.12” (28.45 mm) “-R” Enclosure: 4.50” (114.3 mm) x 2.75” (69.85 mm) x 1.12” (28.45 mm)
Product Weight:
A/RHx-xx-R2 Series: 0.17 lbs. (0.077 kg) A/RHx-xx-R Series: 0.17 lbs. (0.077 kg)
Agency Approvals:
CE, RoHS2, WEEE