Newly redesigned MSCT Series »

RH Duct Platinum RTDs

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

Relative Humidity, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), Duct, ± 2% Accuracy, 100 Ohm RTD (Two Wires), Euro Enclosure

Application

  • Humidification
  • Dehumidification
  • Clean Rooms
  • Data Centers
  • Process Control
  • Schools
  • Hospitals
  • Office Buildings

Product specifications

Supply Voltage:
4-20 mA: 250 Ohm Load: 15 - 40 VDC / 18 - 28 VAC | 500 Ohm Load: 18 - 40 VDC / 18 - 28 VAC 0-5 VDC: 12 - 40 VDC / 18 - 28 VAC | 0-10 VDC: 18 - 40 VDC / 18 - 28 VAC
Supply Current:
Voltage Output: 8 mA maximum (0.32 VA) Current Output: 24 mA maximum (0.83 VA)
Output Load Resistance:
4-20 mA: 700 Ohms maximum 0-5 VDC or 0-10 VDC: 4K Ohms Minimum
Output Signals:
2-wire: 4 - 20 mA (Factory Default) 3-wire: 0-5 or 0-10 VDC and 4 - 20 mA (Field Selectable)
Accuracy @ 77°F (25°C):
Model Dependent: +/- 1% over 20% RH Range between 20 to 90% | +/- 2%, or 3% from 10 to 95%
RH Measurement Range:
0-100%
Operating Humidity Range:
0 to 95% RH, non-condensing (Conformally Coated PCB’s)
Operating Temperature Range:
-40 to 140°F (-40 to 60°C)
Storage Temperature Range:
-40 to 149°F (-40 to 65°C)
RH Stability | Repeatability | Sensitivity:
Less than 2% drift / 5 years | 0.5% RH | 0.1% RH
Response Time (63% Step Change):
20 Seconds Typical
RH Sensor Type:
Capacitive with Hydrophobic Filter
RH Transmitter Stabilization Time:
30 Minutes (Recommended time before doing accuracy verification)
Connections | Wire Size:
Screw Terminal Blocks (Polarity Sensitive) | 16 (1.31 mm²) to 26 AWG (0.129 mm²)
Terminal Block Torque Rating:
4.43 to 5.31 lb-in (0.5 to 0.6 Nm)
NIST Test Points:
Default Test Points: 3 Points (20%, 50% & 80%) 1% NIST Test Points: 5 Points within selected 20% Range (ie. 30%-50% are 30, 35, 40, 45 & 50)
Platinum RTD (PTC) | Number Wires (Wire Colors):
RHx-100-2W Series: (Brown/Brown) & RHx-1K-2W Series: (Black/Black) RHx-100-3W Series: (Brown/Brown/Black) & RHx-1K-3W Series: (Black/Black/White)
Platinum RTD Output @ 32°F (0°C):
RHx-100-xW-D Series: 100 Ohms nominal RHx-1K-xW-D Series: 1000 Ohms nominal
Platinum RTD Tolerance Class:
+/-0.06% Class A | Tolerance Formula: +/-°C = (0.15°C + (0.002 * |t|)
Platinum RTD Din Standard:
DIN EN 60751 (IEC 751)
Temperature Coefficient:
3850 ppm/ °C
Platinum RTD Stability:
+/-0.03% after 1000 Hours @ 572°F (300°C)
Lead Length | Conductor Size:
14” (35.6 cm) | 22 AWG (0.65 mm)
Insulation | Rating:
Etched Teflon (PTFE) Colored Leads | Mil Spec 16878/4 Type E
Enclosure Specifications (Material, Flammability, Temperature, NEMA/IP Rating):
“-EH” Enclosure: ABS Plastic | UL94-V0 | -40 to 140°F (-40 to 60°C) “-4X” Enclosure: Polystyrene Plastic | UL94-V2 | -40 to 158°F (-40 to 70°C) | NEMA 4X (IP 66) “-BB” Enclosure: Aluminum | -40 to 140°F (-40 to 60°C)
Sensing Tube Material | Filter Material:
“EH” Enclosure: 304 Series Stainless Steel | 304 Series Stainless Steel “-4X” Enclosure: Schedule 40 PVC (White) | Slotted PVC without filter “-BB” Enclosure: Schedule 40 PVC (White) | Slotted PVC without filter
Sensing Tube Dimensions (Length x Diameter):
“-EH” Models with Sintered Filters: 7.75” (196.85 mm) x 0.75” (19.05 mm) “-4X” Models: 7.20” (182.88 mm) x 0.840” (21.34 mm) “-BB” Enclosure: 7.20” (182.88 mm) x 0.840” (21.34 mm)
Product Weight:
A/RHx-xx-xW-D Series: 1.22 lbs. (0.55 kg) A/RHx-xx-xW-D-4X Series: 0.50 lbs. (0.227 kg) A/RHx-xx-xW-D-BB Series: 0.90 lbs. (0.41 kg)
Agency Approvals:
CE, RoHS2, WEEE

Related products