Gage Pressure Transducer

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

GP Harness, 2'(0.61m)

Application

  • Refrigeration
  • Fuel Cells
  • Pumps
  • Hydraulics
  • Compressors
  • Robotics
  • Pneumatics
  • Agriculture
  • Spraying Systems
  • Process Control
  • Flow
  • Hydrogen Storage
  • Steam Lines
  • Boilers
  • Chillers

Product specifications

Pressure Transducer Specs Only::
Supply Voltage:
250 Ohm Load: +13 to 30 VDC | 500 Ohm Load: +18 to 30 VDC
Reverse Polarity Protection:
+/- 16 V over 5 minutes
Maximum Load Resistance:
800 Ohms @ 24 VDC | Formula: (Supply VDC – 8 VDC) / 0.020A
Supply Current:
25 mA minimum
Output Signals:
4 to 20 mA (2-Wire, Loop Powered)
Response Time:
< 1 ms
Accuracy @ 22°C (71.6°F):
15 to 60 psig: < +/- 1.0% FS 75 to 300 psig: < +/- 0.5% FS 500 psisg: < +/- 0.5% FS
Stability:
+/- 0.03% FS @ 0 PSIG; +/- 0.12% FS @ 1000 PSIG
Proof Pressure:
3x FS
Burst Pressure:
3x FS
Thermal Shock:
50 Cycles (105ºC to -40ºC, 0.5 hr soaks @ Temp. (10s Transfer))
Vibration (100 to 2000Hz, 20g Sinusoidal, 3 Axes):
300 Cycles (105ºC to -40ºC, 0.5 hr soaks @ Temp. (2s Transfer))
Operating Temperature Range:
-40 to 257ºF (-40 to 125ºC)
Operating Humidity Range:
0 to 95% RH, non-condensing
Storage Temperature Range:
-40 to 176ºF (-40 to 80ºC)
Media Types:
Any gas or liquid compatible with 304L Stainless Steel
Housing Material:
Stainless Steel
Process Fitting Material:
304L Stainless Steel
Process Fitting Size:
1/4”-18 NPT
Recommend Torque Specification:
150 lbs-in (16.95 Nm)
Wiring Connections:
Packard Connector (Cables ordered separately)
Agency Approvals:
RoHS2, WEEE, ISO 9001
EMC Compatibility:
150 V/m
Product Dimensions:
2.60” (66.6 mm) x 0.87” (22.23 mm)
Product Weight:
0.30 lbs. (0.13 kg)
GP Wire Harness Specs Only::
Conductor Size | Conductor Material:
18AWG | Tinned Plated Copper
Lead Wire Insulation | Jacket Color:
Plenum Polyvinylchloride (PVC) | Black
Cable Operating Temperature Range:
0ºC (32ºF) to 75ºC (137ºF)
Rated Application:
Suitable for Indoor and Outdoor(wet) location

Related products