DBL

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

Differential Pressure Switch, 0.08 to 0.8 inWC, SPDT, Auto Reset, NEMA 3 Enclosure

Application

  • Monitoring Filter Blockage
  • Proof of Flow
  • Prove Excessive or Insufficient Flow
  • Alarms and Control

Product specifications

Adjustable Set Point Range:
DBL-205L: 0.08 to 0.8” wc DBL-205B: 0.20 to 2.0” wc DBL-205D: 0.80 to 4.0” wc DBL-205E: 2.0 to 10.0” wc
Adjustable Set Point Switching Differential:
Factory Default: +/- 15% of Trip / Set Point DBL-205L: 0.04 to 0.08" wc DBL-205B: 0.08 to 0.16" wc DBL-205D: 0.40 to 0.80" wc DBL-205E: 0.60 to 1.20" wc
Contact (Load) Rating:
250 VAC maximum, 1.5A Resistive (0.4A Inductive)
Contact Arrangement:
SPDT (Form 1C) w/ Automatic Reset
Media Types:
Air and other non-combustible, non-aggressive gases
Diaphragm Material:
Silicone
Maximum Pressure:
40” wc (10 kPa)
Life Expectancy:
1,000,000 cycles
Operating Temperature Range:
-4 to 185ºF (-20 to 85ºC)
Storage Temperature Range:
-4 to 185ºF (-20 to 85ºC)
Mounting Direction:
Any vertical plane
Enclosure Material:
Base = PA6.6 / Cover = Polystyrene (Transparent)
Enclosure Rating:
NEMA 3 (IP54)
Sample Line Connections:
Accepts 3/16” ID (8mm) Push on plastic/poly tubing
Electrical Connections:
Spade (Maximum 16 AWG (1.5 mm2))
Conduit Knockouts:
Accepts ½” NPT Conduit
Product Dimensions:
4.00” x 2.30” (100 x 58 mm)
Product Weight:
DBL Series: 0.40 lbs (0.20 kg) DBZ-06: 0.16 lbs (0.072 kg)
Agency Approvals:
CE, ISO 9001, RoHS2, WEEE

Related products