This product is covered by ACI's Five (5) Year Limited Warranty. Learn more
Product overview
Power Meter, Bi-Directional, 3 Circuit, ANSI 0.2 Class Accuracy, Ethernet Only, BACNet IP Only, Rogowski Coil Inputs, LCD Display
Application
- Tenant Billing
- Data Centers
- Equipment Load Monitoring
- Industrial Applications
- Predicted Maintenance
- Renewable Energy
- Overhead Cost Reduction
- “NET ZERO” Buildings
- LEED Buildings
- Green Buildings
- Refrigeration
Product specifications
Service Type:
Single Phase, 3 Phase – Four Wire (WYE), Three Phase – Three Wire (Delta)
Power:
100 - 415Vac, 50/60Hz, 100 - 300Vdc on terminals L and N
Burden:
5W
Withstand Voltage:
3250VAC, 50/60Hz for 1 minute
Power Supply Wiring:
AWG22-16 (0.6-1.5mm2)
AC Fuse Protection:
External 1A/250VAC Fuse (Recommended)
Rated Voltage:
100-400VAC Line to Neutral (L-N) or 100-690VAC Line to Line (L-L) RMS for three phase or 100-400VAC RMS for single phase; 100-300 VDC
Number of CT Inputs:
3
Revenue Grade Accuracy:
Active Energy: Class 0.2s (According to IEC 62053-22) and Class 0.2s (According to ANSI C12.20)
Reactive Energy: Class 2 (According to IEC 62053-23) – See Table 2 for parameter accuracy, resolution, and range
Voltage Channels:
400 Volts AC (L-N), 690 VAC (L-L), 45Hz - 65Hz, 300Hz - 500Hz
Withstand Voltage:
1500VAC Continuous, 2500Vac, 50/60Hz for 1 Minute
Input Impedance:
2M ohm per Phase
Pickup Voltage:
10VAC
Current Channels:
3 Channels, 0.525 VAC max, 333 mV CT’s or 0 to 6000 Amps with Rogowski Coils
Maximum Current Input:
150% of current sensor rating (mV CT’s) to maintain accuracy. Up to 6000 Amps w/ Rogowski Coils
Harmonic Resolution:
63rd Harmonic (50Hz or 60Hz type) or 15th Harmonic (400Hz type)
Measurement Type:
Real-time, True RMS measurement of instantaneous Voltage, Current, Power, Frequency, Harmonics, Phase Angle, Demand, Unbalance Factor, Running Time, and Power Factor
Line Frequency:
50/60 Hz
Real Time Parameter Update Rate:
100 mS
Accumulated Parameter Update Rate:
1 Sec
LCD Display:
Multiple Display Modes (Important Parameter’s, All Parameter’s, Settings Display Modes)
Communication Protocol:
Ethernet: BACnet Over IP Only
Enclosure Material | Flammability Rating:
Polycarbonate / UL 94V-0
Operating Temperature Range:
-13 to 158oF (-25 to 70oC)
Storage Temperature Range:
-40 to 185oF (-40 to 85oC)
Operating/Storage Humidity Range:
5 to 95%, non-condensing
Wiring Connections:
Screw Connections
Wire Size:
14-22 AWG (2.5 to 0.34 mm2)
Mounting:
ANSI C39.1 (4” Round) or an IEC 92mm DIN (Square) form
Utility Software:
Acuview Utility Software, Windows Based;
Agency Approvals:
BTL Certified, CE, RoHS2, cULus Listed (File # E359521)
Standard Compliance:
Measurement Standard: IEC 62053-22; ANSI C12.20
Environmental Standard: IEC 60068-2
Safety Standard: IEC 61010-1, UL 61010-1, IEC 61557-12
EMC Standard: IEC 61000-4/-2-3-4-5-6-8-11, CISPR 22, IEC 61000-3-2, IEC 61000-6-2/4
Outlines Standard: DIN 43700, ANSI C39.1
Face Dimensions (L x W x H):
3.80" (96 mm) x 3.80" (96 mm) x 1.99" (50.7 mm)
Product Weight:
0.77 lbs. (350g)