Voltage Output Transmitters

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

Analog Current Sensor, 0-5 VDC, DIN Rail, Split Core, 0-10, 0-20, 0-50 Amp (Default)

Application

  • Load Trending
  • Single Speed Loads
  • Pumps
  • Compressors
  • Fans
  • Preventative Maintenance
  • LEED
  • Project Justification (Calculating ROI)
  • Process Control

Product specifications

Monitored Current Type:
AC Current
Maximum AC Voltage:
600 VAC
Isolation Voltage:
2200 VAC
Operating Frequency Range:
50 to 600 Hz
Core Style:
Solid-Core and Split-Core Versions available (See Ordering Grid)
Supply Voltage:
Induced from the Monitored Conductor (Insulated Conductors only)
Amperage Range:
See Ordering Grid (Field Selectable)
Output Signal | Number of Wires:
A/CTE2 & A/SCTE2 Series: 0 to 5 VDC | A/CTV2 & A/SCTV2 Series: 0 to 10 VDC | 2-Wires
Accuracy:
A/CTE2 & A/SCTE2 Series: (0-10A Range Only): +/- 1% from 5-100% of Selected Range A/CTE2 & A/SCTE2 Series: (All Other Ranges): +/- 1% from 2-100% of Selected Range A/CTV2: +/- 1% from 5-100% of Selected Range A/SCTV2 Series: (0 to 10A Range Only): +/- 2% from 5 to 100% of Selected Range A/SCTV2 Series: (All Other Ranges): +/- 1% from 5 to 100% of Selected Range
Response Time:
< 300 mS (Rise and Fall Times)
Aperture Size:
0.75” (19.05 mm)
DIN Rail Mounting:
35 mm (U.S. Patent No. 7,416,421)
Operating Temperature Range:
5 to 104ºF (-15 to 40ºC)
Operating Humidity Range:
0 to 95%, non-condensing
Storage Temperature | RH Range:
41 to 95ºF (5 to 35ºC) | 40% to 85% RH, non-condensing
Enclosure Material | Flammability Rating:
PC/ABS (Polycarbonate/ABS Blend) | UL94-V0
Wiring Connections:
2 Position, Screw Terminal Block (Polarity Sensitive)
Wire Recommendations:
2 Conductor (Shielded Cable)
Wire Size:
18 to 24 AWG (0.823 mm2 to 0.205 mm2) Copper Wires only
Terminal Block Torque Rating:
4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)
Minimum Mounting Distance:
1” (2.6 cm) between current sensor & other magnetic devices (Relays, Contactors, Transformers)
Agency Approvals:
UL/CUL US Listed (UL 508) Ind. Control Equipment (File # E309723), CE, RoHS2, WEEE
Product Weight:
A/CTE2-xxx & A/CTV2-xxx Series: 0.194 lbs. (0.088 kg) A/SCTE2-xxx & A/SCTV2-xxx Series: 0.274 lbs. (0.125 kg)
Product Dimensions:
Solid Core Versions: 2.760” (70.11 mm) x 3.343” (84.92 mm) x 1.050” (26.67 mm) Split Core Versions: 2.780” (70.51 mm) x 3.238” (82.25 mm) x 1.120” (28.45 mm)