This product is covered by ACI's Five (5) Year Limited Warranty. Learn more
Product overview
Current Transformer, 100A, Solid Core, Measure Canada Approved, 0.77" Aperture, 333mV Output, 1ft Leads
Application
- Tennant Billing
- Load Surveys
- LEED/Green Projects
- ROI / Project Justification
Product specifications
Monitored Current Type:
AC Current
Maximum AC Voltage:
600 VAC, Category III
Core Style:
Solid-Core
Rated Output:
333mV @ 5/20/50/100 Amps (See Ordering Grid)
Operating Frequency Range:
50/60 Hz
Withstand Voltage:
3,000VAC
Accuracy:
0.15% Class IEC 60044-1
Burden:
B0.005
Impulse Insulation (BIL):
10kV
Insulation Resistance:
50 MΩ
Operating Temperature Range:
5 to 140°F (-15 to 60°C)
Storage Temperature Range:
-40 to 185°F (-40 to 85°C)
Operating/Storage Humidity Range:
5 to 95%, non-condensing
Maximum Elevation:
9,842 ft (3 Kilometers)
Enclosure Material | Flammability Rating:
Plastic Encapsulated/UL 94V-0
Wiring Connections:
Stripped and Tinned Lead Wires
Lead Wire Colors:
White: Positive (+)
Black: Negative (-)
Wire Size:
18 AWG (0.75 mm2), UL 1015
Lead Length:
1’ (0.30m)
Agency Approvals:
UL2808, 61010-2, CSA 22.2, CE and RoHS Compliant
Product Weight:
0.2lbs (0.09kg)
Product Dimensions:
2.00" (51.00 mm) x 0.75” (19.00 mm)