Newly redesigned MSCT Series »

Fixed Status Switches

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

Fixed Current Switch, DIN Rail, Solid Core, NC, <0.25A Trip Point, 0 to 250A Range

Application

  • Overload Conditions
  • Underload Conditions
  • Normal Operating Conditions
  • Broken Belts
  • Belt Slippage
  • Locked Rotors
  • Equipment Failure
  • Fans
  • Pumps
  • Compressors
  • Motors
  • Ovens
  • Industrial Equipment
  • Lighting Status and Usage
  • Electrical Load Status
  • Local Alarms (Strobes and Audible Alarms)
  • Preventative Maintenance Scheduling

Product specifications

Monitored Current Type:
AC Current
Maximum AC Voltage:
600 VAC
Operating Frequency Range:
40 to 1 kHz
Core Style:
Solid-Core and Split-Core Versions available (See Ordering Grid)
Sensor Power:
Induced from the Monitored Conductor
Amperage Range:
See Ordering Grid
Isolation Voltage:
2200 VAC
Trip Point Style | Trip Point:
Fixed Trip Point | See Ordering Grid
Contact Type:
Normally-Open “N/O” or Normally-Closed “N/C” (See ordering Grid)
“Status” Contact Rating:
0.2A @ 200 VAC/VDC
“Status” Contact “On” Resistance | “Off” Resistance:
< 10 Ohms (tripped) | > 1 Meg Ohms (Open)
Response Time:
See Response Time Table on back of data sheet
Status LED Indication:
Red LED (Monitored current is above Trip Point)
Aperture Size:
0.75” (19.05 mm)
DIN Rail Mounting:
35 mm | (U.S. Patent No. 7,416,421)
Operating Temperature Range:
5 to 104ºF (-15 to 40ºC)
Operating Humidity Range:
0 to 95%, non-condensing
Storage Temperature | RH Range:
41 to 95°F (5 to 35°C) | 40% to 85% RH, non-condensing
Enclosure Material | Flammability Rating:
PC/ABS (Polycarbonate/ABS Blend) | UL94-V0
Wiring Connections:
2 Position Screw Terminal Block (Not Polarity Sensitive)
Wire Size:
16 to 22 AWG (1.31 mm2 to 0.33 mm2) Copper Wires only
Terminal Block Torque Rating:
4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)
Minimum Mounting Distance:
1” (2.6 cm) between current switch (Relays, Contactors, Transformers)
Agency Approvals:
UL/CUL US Listed (UL 508) Ind. Control Equipment (File # E309723), CE, RoHS2, WEEE
Product Weight:
A/CS2 and A/CSX2: 0.216 lbs. (0.099kg) | A/SCS2 and A/SCSX2: 0.270 lbs. (0.123 kg) A/SCS2-L: 0.280 lbs. (0.127 kg)
Product Dimensions:
Solid Core Versions: 2.760” (70.11 mm) x 3.343” (84.92 mm) x 1.050” (26.67 mm) Split Core Versions: 2.780” (70.51 mm) x 3.238” (82.25 mm) x 1.120” (28.45 mm)

Related products