ACUCT Split Core

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

Current Transformer, 50A, Split Core, 0.75" Aperture, 333mV Output, 2.5m Leads

Application

  • Energy and Demand Metering
  • Load Surveys
  • LEED/Green Projects
  • ROI / Project Justification

Product specifications

Monitored Current Type:
AC Current
Maximum AC Voltage:
600 VAC, Category III
Core Style:
Split-Core (non-hinged)
Rated Output:
333mV @ 50/100/200/300/400/600/800/1000 Amps (see ordering grid)
Operating Frequency Range:
50/60Hz
Withstand Voltage:
3,000VAC
Accuracy:
0.5% from 10-120% of Rated Current, IEC 60044-1
Operating Temperature Range:
5 to 140°F (-15 to 60°C)
Storage Temperature Range:
-40 to 185°F (-40 to 85°C)
Operating/Storage Humidity Range:
5 to 95%, non-condensing
Maximum Elevation:
9,842 ft (3 Kilometers)
Enclosure Material | Flammability Rating:
Epoxy Encapsulated/UL94V-0
Wiring Connections:
Stripped and Tinned Lead Wires
Lead Wire Colors:
White: Positive (+) Black: Negative (-) Bare-Shield (Polarity Sensitive)
Wire Size:
22 AWG (0.34 mm2), 600V Rated VW-1, 105°C White/Brown Twisted Pair (UL 1015)
Lead Length:
8.20’ (2.5m) or 32.80’ (10m) See Ordering Grid
Agency Approvals:
ULR, CE, & RoHS2 Compliant
Product Weight:
AcuCT-075 Series: 0.2lbs (0.09kg) AcuCT-125 Series: 0.3lbs (0.14kg) AcuCT-200 Series: 0.4lbs (0.18kg)
Product Dimensions:
AcuCT-075 Series: 2.00" (50.80 mm) x 2.09" (53.30 mm) x 0.669" (17.00 mm) AcuCT-125 Series: 3.25" (82.50 mm) x 3.35" (85.10 mm) x 1.02" (26.00 mm) AcuCT-200 Series: 4.76" (121.00 mm) x 5.00" (127.00 mm) x 1.18" (30.00 mm)