ACUCT Hinged Split Core

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

Current Transformer, 100A, Hinged Split Core, 1.0" Aperture, 333mV Output, 2.5m Leads

Application

  • Retro Fitting Sub-Metering Electrical Panel
  • Equipment Load Monitoring
  • Industrial Applications
  • Predicted Maintenance
  • Renewable Energy
  • Overhead Cost Reduction
  • “NET ZERO” Buildings
  • LEED Buildings
  • Green Buildings
  • Refrigeration

Product specifications

Monitored Current Type:
AC Current
Maximum AC Voltage:
600 VAC, Category III
Core Style:
Hinged Split-Core
Rated Output:
333mV @ 20/30/40/50/60/100/200 Amps (see ordering grid)
Operating Frequency Range:
50/60Hz
Accuracy:
0.5% from 10-120% of Rated Current
Operating Temperature Range:
5 to 140°F (-15 to 60°C)
Storage Temperature Range:
-40 to 185°F (-40 to 85°C)
Operating/Storage Humidity Range:
5 to 95%, non-condensing
Maximum Elevation:
9,842 ft (3 Kilometers)
Enclosure Material | Flammability Rating:
Black Nylon/UL94V-0
Wiring Connections:
Stripped and Tinned Lead Wires
Lead Wire Colors:
White: Positive (+) Black: Negative (-)
Wire Size:
22 AWG (0.14 mm2), 600V Rated VW-1, 105°C Black/Brown Twisted Pair (UL 1015)
Lead Length:
8.20’ (2.5m) or 32.80’ (10m) See Ordering Grid8.20’ (2.5m) or 32.80’ (10m) See Ordering Grid
Agency Approvals:
ULR, CE, & RoHS2 Compliant
Product Weight:
AcuCT-H040 Series: 0.2lbs (0.09kg) AcuCT-H100 Series: 0.4lbs (0.18kg)
Product Dimensions:
AcuCT-H040 Series: 1.64" (41.66 mm) x 1.16" (29.47 mm) x 1.04" (26.42 mm) AcuCT-H100 Series: 2.76" (70.11 mm) x 2.00" (50.80 mm) x 1.52" (38.61 mm)