Esense Outdoor

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

Carbon Dioxide Sensor, 0-2000 PPM, Heated Enclosure w/ Thermostat, 0-10V or 2-10V/4-20mA Output

Application

  • Outdoor or Non-Heated Structures

Product specifications

Supply Voltage:
24 VAC/VDC ±20%; 50/60Hz (Half-wave rectied)
Power Consumption:
Sensor: <1W Heater: 10W Maximum Total Power: 11W
Enclosure Heater:
24 VAC Turns on @ 39ºF (4ºC) and below
Electrical Connections:
0.00232 in² (1.5 mm²) screw terminals
Operating Temperature Range:
-22ºF to 115ºF (-30ºC to 46ºC)
Operating RH Range:
0 - 95% RH Non-condensing
Warm Up Time:
1 minute (@ full specs 15 minutes)
Accuracy:
±30 ppm and ±3% of reading
Repeatability:
±20 ppm ±1% of measured value
Annual Zero Drift:
± 0.3% of measurement range
Operating Pressure:
+1.6% per 0.145 psi (1 kPa) deviation from normal pressure (1 Atmosphere = 14.7 psi (1.013 KPa))
Sensing Method:
Single beam Non-dispersive Infrared (NDIR)
Sensor Life:
>15 years
Response Time:
<10 seconds @ 30 cc/min ow rate, < 3 minutes diusion time
Operating Environment:
Outdoor or Non-Heated Structures
Sensing Range:
0 to 2000 ppm
Extended CO2 Ranges:
Up to 10,000 ppm (factory set or SADK Kit required)
Extended Range Accuracy>2,000 PPM:
+/- 30 ppm and +/- 5% of reading
Calibration:
Senseair ABC algorithm (Automatic Baseline Correction)
Output Signals:
Standard: Out 1: 0-10V for 0 to 2000 ppm Out 2: 2-10V or 4-20mA for 0 to 2000 ppm
Storage Temperature Range:
-4 to 122ºF (-20 to 50ºC)
Enclosure Material:
Poly Carbonate IP65, Flammability Rating UL94V-0
Dimensions (H x W x D):
(H) 7.62” (193.55 mm) x (W) 4.63” (117.60 mm) x (D) 2.44” (61.98 mm)
Product Weight:
1.4 lbs (0.64 Kg)
Agency Approvals:
EMC Directive 2014/30/EC RoHS Directive 2011/65/EU RoHS 3 Directive 2015/863/EU