Esense Room

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

Carbon Dioxide Sensor, Room Mount, 0-2000 PPM, LCD, 0-5VDC Output

Application

  • Commercial Office Buildings
  • Gymnasiums
  • Shopping Malls
  • Auditoriums
  • Theaters
  • Hospitals & Schools
  • Demand Control Ventilation & Economizers

Product specifications

Supply Voltage:
24 VAC/VDC ±20%; 50/60Hz (Half-wave rectied)
Power Consumption:
<1W
Connections:
0.00232 in² (1.5 mm²) screw terminals
Operating Temperature Range:
32ºF to 122ºF (0ºC to 50ºC)
Operating RH Range:
0 – 95% RH Non-condensing
Warm Up Time:
1 minutes (@ full specs 15 minutes)
Accuracy:
±30 ppm and ±3% of reading
Repeatability:
±20 ppm ±1% of measured value
Annual Zero Drift:
± 0.3% of measurement range
Operating Pressure:
+1.6% per 0.145 psi (1 kPa) deviation from normal pressure (1 Atmosphere = 14.7 psi (1.013 KPa))
Sensing Method:
Single beam Non-dispersive Infrared (NDIR)
Sensor Life:
>15 years
Response Time (T1/e):
<10 seconds @ 30 cc/min ow rate, < 3 minutes diusion time
Operating Environment:
Residential, Commercial spaces
Sensing Range:
0 to 2000 ppm
Extended CO2 Ranges:
Up to 10,000 ppm (factory set or SADK Kit required)
Extended Range Accuracy>2,000 PPM:
+/- 30 ppm and +/- 5% of reading
Coverage Area:
7500 sq. ft. maximum
Mounting:
4-6’ o the oor
:
Display (Optional):
4 digits, 7 segments LCD with ppm indicator
Calibration:
Senseair ABC algorithm (Automatic Baseline Correction)
Analog Outputs:
Standard: Out 1: 0-10V for 0 to 2000 ppm | Out 2: 2-10V or 4-20mA for 0 to 2000 ppm
Storage Temperature Range:
ESENSE-R: -40 to 158ºF (-40 to 70ºC) | ESENSE-R-LCD: -4 to 122ºF (-20 to 50ºC)
Enclosure Material | Flammability Rating:
ABS, Flammability Rating UL94V-0
Dimensions (H x W x D):
(H) 5.12” (130 mm) x (W) 3.35” (85.1 mm) x (D) 1.18” (30 mm)
:
Product Weight (Standard & LCD):
ESENSE-R: 0.294 lbs (0.133 kg) | ESENSE-R-LCD: 0.304 lbs (0.138 kg)
Agency Approvals:
EMC Directive 2014/30/EC | RoHS Directive 2011/65/EU | RoHS 3 Directive 2015/863/EU

Related products