This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
Pulse Width Modulation Input (0.1 to 10 sec), Analog Output(0-10V), (0.02 to 5, 0.59 to 2.93, 0.1 to 25.5s Selectable)
Application
- Pulse to Analog Transducer
- Interface to Variable Speed Pump Drive Control
- Interface to Variable
- Frequency Fan Drive Control
- Interface to Electric Actuator
- Duty Cycle to Analog Control
- Digital to Analog Conversion
Product specifications
Supply Voltage:
24 VDC (24-35 VDC) or 24 VAC (21.6-26.4 VAC), 50/60 Hz
Supply Current:
240 mA maximum using Voltage Output Terminal
125 mA maximum if not using Voltage Output Terminal
Input Pulse Source:
Relay Contact Closure, Transistor or Triac
Input Pulse Trigger Level (@ Impedance):
Normal Mode = 5 to 26.4 VAC/DC | Triac Mode = 9 to 26.4VAC
Output Voltage Signal Range (@ Impedance):
PTA: 0-1 VDC | 0-4 VDC | 0-10 VDC | 0-13 VDC | 1-2 VDC | 1-5 VDC | 1-11 VDC | 1-14 VDC
PTA2: 0-10 VDC @ 400 ohms minimum
Output Voltage Adjustable Signal Ranges:
PTA Only: 0-20 VDC (with adjustable offset)
Output Voltage Impedance:
PTA Only: 3300Ω minimum at 20 VDC +/- 10% | 400Ω minimum at 10 VDC +/- 10%
Output Current Fixed Signal Ranges:
PTA Only: 0-16 mA, 4-20 mA
Output Current Adjustable Signal Ranges:
PTA Only: 0-20 mA (with adjustable offset)
Output Current Impedance:
PTA Only: 0 to 750Ω maximum
Resolution:
256 steps of resolution
Accuracy:
PTA:+/- 2% of span for adjustable ranges, 5% for preset (60 Hz)
PTA:+/- 3% of span for adjustable ranges, 5% for preset (50 Hz)
PTA2: +/- 5%
Regulated Power Output (User):
24 VDC, 48 mA maximum
Connections:
90° Pluggable Screw Terminal Blocks
Wire Size:
16 (1.31 mm2) to 26 AWG (0.129 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating RH Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
PTA: (L) 3.75” (W) 2.20” (H) 1.15” (95.25 x 55.88 x 29.21 mm)
PTA2: (L) 2.20” (W) 2.35” (H) 1.00” (55.88 x 59.69 x 25.4 mm)
Product Weight:
PTA: 0.24 lbs. (0.1077 Kg)
PTA2: 0.18 lbs. (0.082 Kg)
Agency Approvals:
RoHS2, WEEE