This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
Pressure Input (3-15PSI), Analog Output (4-20mA), (1-5V, 2-10V, 3-15V Selectable)
Application
- Building Automation
- Process Control
- Pneumatic System Monitoring
- Pneumatic to Proportional Analog Output
Product specifications
Supply Voltage:
24 VDC or 24 VAC, -6%/+10%
Supply Current:
50 mA maximum @ 24 VDC
Output Signals:
1-5 VDC @ 250Ω | 2-10 VDC @ 500Ω | 3-15 VDC @ 750Ω | 4-20 mA @ 500Ω
Input Pressure Range:
PTP 3-15: 3 to 15 psig | PTP 3-30: 3 to 30 psig
Accuracy:
2% full scale at room temperature | 3% full scale across operating temperature range
Filtering:
Furnished with integral-in-barb 80-100 micron filter (Part # PN004)
Connections:
90° Pluggable Screw Terminal Blocks
Wire Size:
16 (1.31 mm2) to 26 AWG (0.129 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Connections | Pneumatic Tubing Size-Type:
1/4" O.D. nominal (1/8” I.D.) polyethylene
Pneumatic Fitting:
Removeable brass barbed fitting in machined aluminum manifold
Plugged 1/8-27-FNPT gauge port | Gauge installed at additional cost
Gauge Pressure Range (Gauge Models):
0-30 psig (0-200 kPa)
Gauge Pressure Accuracy (Gauge Models):
± 2.5% Midscale (± 3.5% Full Scale)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating RH Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
No Gauge: (L) 3.25” (W) 2.18” (H) 1.87” (82.55 x 55.37 x 47.49 mm)
With Gauge: (L) 3.25” (W) 2.18” (H) 2.95” (82.55 x 55.37 x 74.93 mm)
Product Weight:
No Gauge: 0.28 lbs. (0.1276 Kg) | With Gauge: 0.37 lbs. (0.170 Kg)
Agency Approvals:
RoHS2, WEEE