This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
Floating Point Input (90 sec), Pressure Output (0-15PSI), Dual Valve, Maintains Branch Pressure, (0-10PSI, 5-15PSI Selectable)
Application
- Pneumatic Damper Motor Control
- Pneumatic Valve Actuator Control
- Compressor Staging
- Electric Control of any Pneumatic Actuator
Product specifications
Supply Voltage:
24 VAC +/-10% at terminals
Supply Current:
PTS4.1: 350mAAC, 200mADC Maximum
Digital Input Signal Source:
Two (2) Relay Contact Closures, Transistors or TRIACs (no accessories required)
Digital Input Signal Trigger Level (@ Impedance):
9-24 VAC @ 750Ω
Rate of Change:
90 Seconds
Air Supply Pressure:
25 psig (172 kPa) maximum, 20 psig (138 kPa) minimum
Output Pressure Range (Jumper Selectable):
0-10 psig (0-68.95 kPa), 5-15 psig (34.47-103.43 kPa), or 0-15 psig (0-103.43 kPa)
Accuracy:
2% @ room temperature, 3% @ full range of operating temperature
Air Flow:
Supply valves @ 20 psig (138 kPa) main/15 psig (103 kPa) out, 2300 scim, Branch Line requires 2 in3 or 33.78 cm3 (min) | Unit requires min. of 25 ft of 1/4” O.D. poly tubing
Filtering:
Furnished with integral-in-barb 80-100 micron filter (Part # PN004)
Connections:
90° Pluggable Screw Terminal Blocks
Wire Size:
16 (1.31 mm2) to 26 AWG (0.129 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Connections | Pneumatic Tubing Size-Type:
1/4” O.D. nominal (1/8” I.D.) polyethylene
Pneumatic Fitting:
Removeable brass barbed fittings for Main and Branch in machined aluminum manifold Plugged 1/8-27-FNPT gauge port | Gauge installed at additional cost
Gauge Pressure Range (Gauge Models):
0-30 psig (0-200 kPa)
Gauge Pressure Accuracy (Gauge Models):
± 2.5% Midscale (± 3.5% Full Scale)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating Humidity Range:
10 to 95% non-condensing
Storage Temperature Range:
-10 to 150°F (-23.3 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
No Gauge: (L) 3.25” (W) 2.18” (H) 1.87” (82.55 x 55.24 x 47.49 mm)
With Gauge: (L) 3.69” (W) 2.30” (H) 2.95” (93.60 x 58.42 x 74.9 mm)
Product Weight:
0.61 lbs. (0.276 Kg)
Agency Approvals:
RoHS2, WEEE