This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
Floating Point Input (45 sec), Pressure Output (0-15PSI), Dual Valve, Maintains Branch Pressure , Gauge, (90, 60, 120 sec), (0-15PSI, 0-20PSI)
Application
- Three Way Mixing Valve Control
- Chiller Loading
- Pilot Positioner Control
- Fan Vane Control
- Compressor Staging
Product specifications
Supply Voltage:
24 VAC (+/-10%), 50 or 60Hz, 24 VDC (+10%/- 5%)
Supply Current:
EFP: 300mAAC, 200mADC Maximum | EFP2: 350mAAC, 200mADC | EFP2FS: 500mAAC, 200mADC
Digital Input Signal Source:
Relay Contact Closure, Transistor or Triac
Digital Input Signal Level (@ Impendence):
9-24 VAC/VDC @ 750Ω
Digital Input Rates of Change:
See Ordering Grid
Manual / Auto Override Switch:
MAN function = output can be varied | AUTO function = output is controlled from input signal
Manual / Auto Override Feedback Output:
24 VDC/VAC @ 1A maximum, N.O. in AUTO operation (Optional: N.O. in MAN operation)
Feedback Output Signal Range:
0-5 VDC = Output Span
Air Supply Pressure:
Maximum 25 psig (172.369 kPa), minimum 22 psig (151.69 kPa)
Air Supply Consumption:
2300 SCIM (37.69 liters)
Output Pressure Range (Jumper Selectable):
0-10 psig (0-68.95 kPa), 0-15 psig (0-103.43 kPa) or 0-20 psig (137.9 kPa)
Output Pressure Accuracy:
2% full scale at room temperature (above 1 psig or 6.895 kPa)
3% full scale across operating temperature range (above 1 psig)
Air Flow:
Supply valves @ 20 psig (138 kPa) main/15 psig (103 kPa) out, 2300 scim
Branch Line requires 2 in3 or 33.78 cm3 (minimum) | Min. 25 ft of 1/4” O.D. poly branch tubing
Filtering:
Furnished with integral-in-barb 80-100 micron filter (Part # PN004)
Optional standard barb (PN002) with external 5 micron in-line filter (PN021)
Connections | Wire Size:
90° Pluggable Screw Terminal Blocks | 16 (1.31 mm2) to 26 AWG (0.129 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Connections | Pneumatic Tubing Size-Type:
1/4” O.D. nominal (1/8” I.D.) polyethylene
Pneumatic Fitting:
Removeable brass fittings for Main & Branch in machined manifold, Plugged 1/8-27-FNPT gauge port
Gauge Pressure Range (Gauge Models):
0-30 psig (0-200 kPa)
Gauge Pressure Accuracy (Gauge Models):
± 2.5% Midscale (± 3.5% Full Scale)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating Humidity Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
No Gauge: (L) 4.00” (W) 3.25” (H) 1.87” (101.60 x 82.55 x 47.50 mm)
With Gauge: (L) 4.00” (W) 3.25” (H) 2.95” (101.60 x 82.55 x 74.97 mm)
Product Weight:
EFPG: 0.596 lbs. (0.2703 Kg) | EFP2G: 0.76 lbs. (0.3459 Kg) | EFP2GF: 0.70 lbs. (0.3175 Kg)
Agency Approvals:
RoHS2, WEEE