AUD

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

Floating Point Input (5 sec), Analog Output, Version 1, (15, 30, 90 sec Selectable)

Application

  • Variable Speed Drive Control
  • Motor Speed Control
  • Contact Integration
  • Floating Point to Analog Conversion
  • Positioner and Actuator Control

Product specifications

Supply Voltage:
24 VDC (24 VDC to 35 VDC) or 24 VAC (21.6 VAC to 28 VAC), 50/60 Hz.
Supply Current:
208 mA maximum
Input Signal Source:
Relay contact closure, transistor, or triac (24 VAC, 50/60 Hz)
Input Signal Trigger Level:
Normal Mode: 5 to 26.4 VDC, 24 to 26.4 VAC Triac Mode: 24 to 26.4 VAC
Input Full Range Rates of Change:
See Ordering Grid
Output Voltage Fixed Signal Ranges:
0 to 1 VDC, 0 to 4 VDC, 0 to 10 VDC, 0 to 13 VDC, 1 to 2 VDC, 1 to 5 VDC, 1 to 11 VDC, 1 to 14 VDC
Output Voltage Adjustable Signal Ranges:
0 to 20 VDC (with adjustable offset and span)
Output Voltage Signal Load:
3300Ω minimum at 20 VDC ± 10% , 400 ohms minimum at 10 VDC ± 10% (If the voltage output is limited to 18 VDC on the high end of the output span, the DC supply limit can be 24 VDC –10% and maintain stated accuracy
Output Current Fixed Signal Ranges:
0 to 16 mA, 4 to 20 mA
Output Current Adjustable Signal Ranges:
0 to 20 mA (with adjustable offset and span)
Output Current Signal Load:
0 to 750Ω maximum (If the load is lowered to 700Ω, the DC supply can be 24 VDC –10% and maintain stated accuracy
Output Signal Accuracy (24 VAC, 60 Hz):
Absolute +/- 2% of span for adjustable ranges, 5% for preset
Output Signal Accuracy (24 VAC, 50 Hz):
Absolute +/- 3% of span for adjustable ranges, 5% for preset
Output Signal Resolution:
256 steps (all ranges)
Regulated Power Output (User):
24 VDC (+/- 10%), 48 mA maximum
Connections:
90° Pluggable Screw Terminal Blocks
Wire Size:
16 (1.31 mm2) to 26 AWG (0.129 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating Humidity Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
(L) 3.75” (W) 2.20” (H) 1.15” (95.25 x 55.88 x 29.21 mm)
Product Weight:
0.24 lbs. (0.1077 Kg)
Agency Approvals:
RoHS2, WEEE

Related products