This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
Analog Input (0-5VDC), Pressure Output (0-15PSI), Single Valve, 0.007" Bleed Orifice, (0-10V, 0-15V, 0-20mA Selectable)
Application
- Three Way Mixing Valve Control
- Chiller Loading
- Pilot Positioner Control
- Pneumatic Valve & Damper Actuator Control
- Fan Vane Control
- DDC Control
- Above Ceiling Applications (Mixing & VAV Boxes)
Product specifications
Supply Voltage:
24 VAC (+/- 10%), 50 or 60Hz, 24 VDC (+10% /-5%)
Supply Current:
300 mAAC, 200mADC Maximum | 400mAAC, 200mADC on fail safe models
Input Signal Source:
0-5 VDC @ 10,000 Ω | 0-10 VDC @ 10,000Ω | 0-15 VDC @ 10,000Ω | 0-20 mA @ 250Ω
Feedback Output Signal Range:
0-5 VDC = Output Span
Output Pressure Range:
0 to 15 psig (0-103.421 kPa) maximum
Air Supply Pressure:
Maximum: 25 psig (172.369 kPa) | Minimum: 18 psig (124.106 kPa)
Output Pressure Accuracy:
1% full scale @ room temperature | 2% full scale across operating temperature range
Manual / Auto Override Switch:
MAN function = output can be varied | AUTO function = output is controlled from input signal
Air Flow:
Supply valves @ 20 psig (138 kPa) main/15 psig (103 kPa) out, 2300 scim
Branch Line requires 2 in3 or 33.78 cm3 (min.). Branch line min. of 25 feet of 1/4” O.D. poly tubing
Filtering:
Furnished with integral-in-barb 80-100 micron filter (Part # PN004) except for PXP2LG which is furnished with external 5 micron in-line filter (PN021)
Connections:
90° Pluggable Screw Terminal Blocks
Wire Size:
16 (1.31 mm2) to 26 AWG (0.129 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Connections | Pneumatic Tubing Size-Type:
1/4” O.D. nominal (1/8” I.D.) polyethylene
Pneumatic Fitting:
Removeable brass barbed fittings for Main and Branch in machined aluminum manifold
Plugged 1/8-27-FNPT gauge port | Gauge installed at additional cost
Gauge Pressure Range (Gauge Models):
0-30 psig (0-200 kPa)
Gauge Pressure Accuracy (Gauge Models):
± 2.5% Midscale (± 3.5% Full Scale)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating RH Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
No Gauge: (L) 3.25” (W) 2.18” (H) 1.87” (82.55 x 55.37 x 47.49 mm)
With Gauge: (L) 3.25” (W) 2.18” (H) 2.95” (82.55 x 55.37 x 74.9 mm)
Product Weight:
PXP1.3: 0.40 lbs. (0.1814 Kg) | PXP2.3: 0.47 lbs. (0.2126 Kg) | PXP1.3G: 0.49 lbs. (0.2211 Kg)
PXP2.3G & PXP2.3GFS: 0.59 lbs. (0.2693 Kg)
Agency Approvals:
RoHS2, WEEE