This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
PWM/Analog/Floating Point to Resistance Output, 0 to 135 Ohm Resistance Network, Plastic Enclosure
Application
- Electronic Potentiometer
- Resistive Sensor Simulation
Product specifications
Supply Voltage:
24 VAC or 24 VDC, +/-10%
Supply Current:
130 mA maximum
Input Voltage Signal Range (@ Impedance):
0 to 5 VDC | 1 to 5 VDC | 0 to 10 VDC | 2 to 10 VDC @ 100,000Ω
Input Current Signal Range (@ Impedance):
0-20 mA, 4 to 20 mA @ 250Ω
Input Pulse Source:
Relay Contact Closure, Transistor, Triac (Adapter Required)
Input Pulse Trigger Level (@ Impedance):
5-24 VDC/VAC
Off Time Between Pulses:
80 milliseconds
Floating Point / Tri-State Input Signal Source:
Relay, Contact Closure, Transistor, or Triac (Adapter Required)
Floating Point / Tri-State Rates of Change:
55 seconds for full output span
Floating Point / Tri-State Input Signal Trigger Level:
5-24 VDC/VAC
Output Resistance Range:
0 to 135Ω (3 watts)
Resolution:
32 steps
Digital Output Type:
Form “C” Relays
Relay Contact Rating:
1A @ 30 VDC / 125 VAC
Relay Electrical Life:
100,000 operation @ 1A
Relay Mechanical Life:
10,000,000 operations
Connections | Wire Size:
Color coded 18 AWG wire leads with spade connectors
Mounting:
Mounts directly to ½” knockout on actuator housing
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating Humidity Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
(L) 2.40” (W) 3.80” (H) 1.00” (60.96 x 96.52 x 25.4 mm)
Product Weight:
0.43 lbs. (0.196 Kg)
Agency Approvals:
RoHS2, WEEE