6N1 ISO

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

6 Digital Inputs to 1 Analog Output, Stage Control (Stage Control)

Application

  • Coldest Zone Hot Deck Reset
  • Signal Selector
  • 3 Stage SCR

Product specifications

Supply Voltage:
24 VAC (+/- 10%), 50/60 Hz
Supply Current:
255 mA maximum (6.12VA with a 24 volt power supply)
Power Output:
24 VDC or 15 VDC (Jumper Selectable)
Power Output (Supply Current):
100 mA maximum
Input Voltage Signal Range/Input Impedance (6N1-ISO):
0 to 5 VDC @ 1MΩ, 0 to 10 VDC @ 20,000Ω, 0 to 20 VDC @ 10,000Ω
Input Current Signal Range/Input Impedance (6N1-ISO):
0-20 mA @ 249Ω
Input Mode (Digital/Binary) (6N1-ISO & 6N1-ISO-STG):
15 VDC, 24 VDC or 24 VAC +/-10% @ 100,000Ω
One Analog Signal Output (@ Impedance):
0-5 VDC @ 1000Ω | 0-10 VDC @ 1000Ω | 0-20 VDC @ 1000Ω | 0-20 mA @ 500Ω maximum
Output Signal Accuracy (24 VAC, 50 Hz):
+/- 2% of full scale
Resolution:
64 steps of resolution
Product Functions(6N1-ISO):
Average, Highest, Lowest, Sum, Difference
Product Functions (6N1-ISO-STG):
Stage Control
Connections:
90° Pluggable Screw Terminal Blocks
Wire Size:
16 (1.31 mm2) to 26 AWG (0.129 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating RH Range:
10 to 90% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
(L) 4.00” (W) 4.60” (H) 1.00” (101.6 x 116.84 x 25.4 mm)

Related products