This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
Analog input, Relay Output, 4 (SPDT) Relays, 3% Deadband
Application
- Level Indication
- Digital Output Expansion
- Alarms
- Staging and Sequencing
Product specifications
Supply Voltage:
24 VAC (+/- 10%), 50/60 Hz or 22-28 VDC
Supply Current:
180 mA maximum
Input Voltage Signal Range (@ Impedance):
0 to 12 VDC @ 10MΩ, 0 to 24 VDC @ 20,000Ω
Input Current Signal Range (@ Impedance):
0-20 mA @ 500Ω
Deadband (0-12 VDC Signal):
3% Version (Standard): 0.33 VDC | 10% Version: 1.0 VDC
Deadband (0-24 VDC Signal):
3% Version (Standard): 0.66 VDC | 10% Version: 2.0 VDC
Deadband (0-20 mA Signal):
3% Version (Standard): 0.66 mA | 10% Version: 2.0 mA
Digital Output Type:
Four SPDT Form "C" Relays
Relay Contact Rating:
2A @ 24 VDC, 0.5A @ 240 VAC
Relay Electrical Life:
100,000 operations @ 1A
Relay Mechanical Life:
10,000,000 operations
Connections:
45° Captive screw Terminal Blocks
Wire Size:
12 (3.31 mm2) to 22 AWG (0.33 mm2
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating RH Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
(L) 2.75" (69.85 mm) x (W) 3.25" (82.55 mm) x (H) 1.00" (25.4 mm)
Product Weight:
0.25 lbs. (0.113 kg)
Agency Approvals:
RoHS2, WEEE