AFP

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

Analog Input (0-5VDC), Floating Point Output (60 sec), Version #1, (30, 90s Selectable)

Product specifications

Supply Voltage:
24 VAC or 24 VDC, (+/- 10%), 50/60 Hz
Supply Current:
105 mA maximum without 24 VDC auxiliary output 190 mA maximum with 24 VDC auxiliary output
Input Voltage Signal Range (@ Impedance):
0-5 VDC, 0-10 VDC, 0-15 VDC
Input Current Signal Range (@ Impedance):
0-20 mA
Analog Voltage Signal Input Range with Offset Jumper:
1-5 VDC, 2-10 VDC, 3-15 VDC
Analog Current Signal Input Range with Offset Jumper:
4-20 mA
Input Impedance:
Voltage @ 10,000Ω Nominal / Current @ 250Ω nominal
Output (Floating Point):
Two relay contact outputs (Increase / Decrease)
Relay Contact Rating:
Dry Contact, Form C, 2A maximum @ 24 VDC
Relay Electrical Life:
100,000 operations minimum
Relay Mechanical Life:
1,000,000 operation
Connections:
90° Pluggable Screw Terminal Blocks
Wire Size:
16 (1.31 mm2) to 26 AWG (0.129 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating RH Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
UL94 V-0
Product Dimensions:
(L) 4.00” (W) 3.25” (H) 1.15” (101.6 x 82.55 x 29.21 mm)
Product Weight:
0.325 lbs. (0.147 Kg)
Agency Approvals:
RoHS2, WEEE

Related products