DRN3

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

PWM/Analog/Floating Point to Resistance Output, Selectable Resistance Network

Application

  • Electronic Potentiometer
  • Electric Actuator Control
  • Resistive Sensor Simulation

Product specifications

Supply Voltage:
24 VAC +/- 10%, 24 VDC +25% / -8%
Supply Current:
250 mA maximum
Input Voltage Signal Range (@ Impedance):
0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, 2 to 10 VDC, 0 to 15 VDC, 3 to 15 VDC @ 10,000Ω
Input Current Signal Range (@ Impedance):
0-20 mA, 4 to 20 mA @ 250Ω
Input Pulse Source:
Relay Contact Closure, Transistor, Triac
Input Pulse Trigger Level (@ Impedance):
7-30 VDC, 10-26.4 VAC @ 750Ω
Floating Point / Tri-State Rates of Change:
See Ordering Grid
Floating Point / Tri-State Input Signal Trigger Level:
5-24 VDC/VAC
Digital Output Type:
Form “C” Relays
Resolution:
256 Steps (No wrap around)
Relay Contact Rating:
2A @ 24 VDC, 0.5A @ 240 VAC
Relay Electrical Life:
100,000 operation @ 1A
Relay Mechanical Life:
10,000,000 operations
Connections:
45° Captive screw Terminal Blocks
Wire Size:
12 (3.31 mm2) to 22 AWG (0.33 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating RH Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
(L) 5.00” (W) 3.23” (H) 1.00” (127.00 x 81.99 x 25.40 mm)
Product Weight:
0.45 lbs. (0.2041 Kg)
Agency Approvals:
RoHS2, WEEE