ARM

Please Enter the Span of your Transmitter

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

Analog Input, Analog Output, Analog Rescaling Module. Factory Calibration option is available for an additional charge. This will speed up installation time for the end user. Please enter the Input and Output span.

 

Application

  • Resistance to Current or Voltage Conversion
  • Voltage to Current or Voltage Conversion
  • Current to Current or Voltage Conversion
  • Shrink or Expand Sensor Ranges
  • Increase Analog Input Resolution
  • Reverse a Signal
  • Adapt Non-compatible Signals

Product specifications

Supply Voltage:
24 VAC or 24 VDC, (+/- 10%), 50/60 Hz
Supply Current:
200 mA maximum
Input Voltage Signal Range (@ Impedance):
0-35 VDC @ 1,000,000Ω
Input Current Signal Range (@ Impedance):
0 to 44 mA @ 250Ω
Input Resistance Signal Range:
0 to 500,000Ω
Field Adjustable “Operate” Range:
Multi-turn potentiometers
Output Voltage Signal Range (@ Impedance):
0.25 VDC minimum to 20 VDC maximum
Output Current Adjustable Signal Ranges:
44 mA maximum, Signal Gain 1 to 25 times (nominal) depending on input value
Accuracy:
+/- 1%
Output Signal Attenuation:
0 to 100%
Output Signal Offset:
0.25 to 20 VDC
Output Signal Inversion (RA):
20 to 0.25 VDC (nominal)
Output Current Signal Load:
750Ω @ 20 mA
Output Voltage Signal Load:
3300Ω @ 20 VDC +/- 10% / 400Ω @ 10 VDC +/- 10%
Regulated Power Output (User):
20 VDC +/- 10%, 30 mA maximum
Connections:
45° Captive screw Terminal Blocks
Wire Size:
12 (3.31 mm2) to 22 AWG (0.33 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating Humidity Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
(L) 3.69” (W) 2.17” (H) 1.00” (93.73 x 55.12 x 25.54 mm)
Product Weight:
0.200 lbs. (0.0907 Kg)
Agency Approvals:
RoHS2, WEEE