ARM

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

Analog Input, Analog Output, Analog Rescaling Module

Application

  • Resistance to Current or Voltage Conversion
  • Voltage to Current or Voltage Conversion
  • Current to Current or Voltage Conversion
  • Shrink or Expand Sensor Ranges
  • Increase Analog Input Resolution
  • Reverse a Signal
  • Adapt Non-compatible Signals

Product specifications

Supply Voltage:
24 VAC or 24 VDC, (+/- 10%), 50/60 Hz
Supply Current:
200 mA maximum
Input Voltage Signal Range (@ Impedance):
0-35 VDC @ 1,000,000Ω
Input Current Signal Range (@ Impedance):
0 to 44 mA @ 250Ω
Input Resistance Signal Range:
0 to 500,000Ω
Field Adjustable “Operate” Range:
Multi-turn potentiometers
Output Voltage Signal Range (@ Impedance):
0.25 VDC minimum to 20 VDC maximum
Output Current Adjustable Signal Ranges:
44 mA maximum, Signal Gain 1 to 25 times (nominal) depending on input value
Accuracy:
+/- 1%
Output Signal Attenuation:
0 to 100%
Output Signal Offset:
0.25 to 20 VDC
Output Signal Inversion (RA):
20 to 0.25 VDC (nominal)
Output Current Signal Load:
750Ω @ 20 mA
Output Voltage Signal Load:
3300Ω @ 20 VDC +/- 10% / 400Ω @ 10 VDC +/- 10%
Regulated Power Output (User):
20 VDC +/- 10%, 30 mA maximum
Connections:
45° Captive screw Terminal Blocks
Wire Size:
12 (3.31 mm2) to 22 AWG (0.33 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating Humidity Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
(L) 3.69” (W) 2.17” (H) 1.00” (93.73 x 55.12 x 25.54 mm)
Product Weight:
0.200 lbs. (0.0907 Kg)
Agency Approvals:
RoHS2, WEEE