This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
Analog Input, Analog Output, Analog Isolation Module w/ Rescaling
Application
- Grounded Electrical Actuator Isolation
- Florescent Light Dimmer Isolation
- Ground Loop Isolation
- Variable Frequency Motor Drive Isolation
- General Analog Signal Input and Output Isolation
Product specifications
Supply Voltage:
24 VAC (+/- 10%), 50/60 Hz
Supply Current:
200 mA maximum
Input Voltage Signal Preset Ranges:
0-5V, 0-10V, 0-15V, 0-20V, 1-5V, 2-10V, 3-15V, 4-20V, 0-1V
Input Current Signal Preset Ranges:
0-20 mA, 4-20 mA, 0-1 mA
Input Signal Adjustable Voltage Span:
1 VDC (Minimum) to 20 VDC (Maximum)
Input Signal Adjustable Voltage Offset:
From 0 to 20 VDC
Input Signal Adjustable Current Span:
4 mA (Minimum) to 20 mA (Maximum)
Current Offset:
From 0 to 20 mA
Input Voltage Impedance:
9,500Ω
Input Current Impedance:
250Ω +/-1%
Output Voltage Signal Preset Ranges:
0-5 VDC, 1-5 VDC, 0-10 VDC, 2-10 VDC
Output Current Signal Preset Ranges:
0-20 mA, 4-20 mA
Output Signal Adjustable Voltage Span:
1 VDC (Minimum) to 20 VDC +/- 1 VDC (Maximum)
Output Signal Adjustable Voltage Offset:
From 0 to 10 VDC
Output Signal Adjustable Current Span:
0 mA (Minimum) to 20 mA (Maximum)
Output Signal Adjustable Current Offset:
From 0 to 20 mA
Output Voltage Impedance:
5,000Ω
Output Current Impedance:
500Ω
Accuracy:
+/- 3%
Linearity:
+/- 1%
Analog Optical Isolation:
600VAC / 1500 VDC Maximum
Connections:
45° Captive screw Terminal Blocks
Wire Size:
12 (3.31 mm2) to 22 AWG (0.33 mm2)
Terminal Block Torque Rating:
0.5 Nm (Minimum); 0.6 Nm (Maximum)
Operating Temperature Range:
35 to 120°F (1.7 to 48.9°C)
Operating RH Range:
10 to 95% non-condensing
Storage Temperature Range:
-20 to 150°F (-28.9 to 65.5°C)
Snaptrack Material:
Polyvinyl Chloride (PVC)
Snaptrack Flammability Rating:
UL94 V-0
Product Dimensions:
(L) 4.60” (W) 3.23” (H) 1.20” (116.84 x 81.90 x 30.48 mm)
Product Weight:
0.525 lbs. (0.238 Kg)
Agency Approvals:
RoHS2, WEEE