BACnet Duct Humidity

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

BACnet MS/TP, Modbus RTU, Relative Humidity, Duct, Euro Enclosure

Application

  • Humidification
  • Dehumidification
  • Supply / Discharge / Return Air
  • Economizers
  • Clean Rooms
  • Data Centers
  • Process Control
  • Schools
  • Hospitals
  • Office Buildings

Product specifications

Supply Voltage:
12 to 36 VDC / 24 VAC +/- 10%, 50/60 Hz (Reverse Polarity Protected)
Supply Current:
25 mA maximum (0.67 VA)
Temperature Measurement Range:
-40 to 176ºF (-40 to 80ºC)
Accuracy @ 77°F (25°C):
Temperature: +/- 1.0ºF (+/- 0.5ºC)
Temperature Calibration Offset:
+/- 9ºF (+/- 5ºC) (Field Configurable)
Temperature Units:
ºF (Factory Default), ºC, ºK (Field Configurable)
RH Measurement Range:
0 to 100%
RH Accuracy @ 77°F (25°C):
+/- 2% from 10 to 90% RH
RH Calibration Offset:
+/- 10% RH (Field Configurable)
Resolution:
+/- 0.1º | +/- 0.1%
Output Update Rate:
4 seconds
Communication Protocol:
BACnet™ MS/TP or Modbus RTU = Field Selectable; EIA RS-485
Network Addressable:
0 = Factory Default | 1-127 = Field Selectable
Supported Baud Rates:
Auto Baud (Factory Default) | 9600, 19200, 38400, 57600, 76800, 115200 (Field Selectable)
Modbus Data Bits / Parity / Stop Bit:
8 Data Bits | None/Even/Odd = Field Selectable | 1 or 2= Field Selectable
Maximum Distance:
4000 ft (1219 m)
End of Line Termination Resistance:
120 Ohms Termination Resistance (Field Selectable)
Tri-Color Status LED:
Connection Status
Connections | Wire Size:
Screw Terminal Blocks | 16 AWG (1.31 mm2) to 22 AWG (0.33 mm2)
Transmitter Operating Temperature Range:
-40 to 176ºF (-40 to 80ºC)
Storage Temperature Range:
-40 to 185ºF (-40 to 85ºC)
Operating Humidity Range:
10 to 95% RH, non-condensing
Probe Material:
304 Stainless Steel
Filter Material:
304 Stainless Steel
Probe Diameter:
0.750” (19.05 mm)
Enclosure Material | Flammability Rating:
ABS Plastic | UL94-HB
Enclosure Temperature Rating:
-40 to 140ºF (-40 to 60ºC)
Foam Pad Material | Flammability Rating:
Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
Product Dimensions:
10.06” (255.53 mm) x 4.30” (109.22 mm)
Product Weight:
1.30 lbs. (0.59 kg)
Agency Approvals:
BTL Certified, CE, RoHS, WEEE, China RoHS