BACnet Outside

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

BACnet MS/TP, Modbus RTU, Relative Humidity Sensor, Outside, Euro Enclosure

Application

  • Outdoor Air Temperature and RH Sensing
  • Economizers
  • Warehouse Facilities
  • Cold Storage Buildings
  • Manufacturing Plants
  • Wash Down Environments

Product specifications

Supply Voltage:
12 to 36 VDC / 24 VAC +/- 10%, 50/60 Hz (Reverse Polarity Protected)
Supply Current:
25 mA maximum (0.67 VA)
Temperature Measurement Range:
-40 to 176ºF (-40 to 80ºC)
Accuracy @ 77°F (25°C):
+/- 1.0 ºF (+/- 0.5ºC)
Temperature Calibration Offset:
+/- 9ºF (+/- 5ºC) (Field Configurable)
Temperature Units:
ºF (Factory Default), ºC, ºK (Field Configurable)
RH Measurement Range:
0 to 100%
RH Measurement Range:
+/- 2% from 10 to 90% RH
RH Calibration Offset:
+/- 10% RH (Field Configurable)
Resolution:
+/- 0.1º | +/- 0.1%
Output Update Rate:
4 seconds
Communication Protocol:
BACnet™ MS/TP or Modbus RTU = Field Selectable; EIA RS-485
Network Addressable:
0 = Factory Default | 1-127 = Field Selectable
Supported Baud Rates:
Auto Baud (Factory Default) | 9600, 19200, 38400, 57600, 76800, 115200 (Field Selectable)
Modbus Data Bits / Parity / Stop Bit:
8 Data Bits | None/Even/Odd = Field Selectable | 1 or 2= Field Selectable
Maximum Distance:
4000 ft (1219 m)
End of Line Termination Resistance:
120 Ohms Termination Resistance (Field Selectable)
Tri-Color Status LED:
Connection Status
Connections | Wire Size:
Screw Terminal Blocks | 16 AWG (1.31 mm2) to 22 AWG (0.33 mm2)
Transmitter Operating Temperature Range:
-40 to 176ºF (-40 to 80ºC)
Storage Temperature Range:
-40 to 185ºF (-40 to 85ºC)
Operating RH Range:
10 to 95% RH, non-condensing
RH Sensing Tube | Diameter:
Aluminum | 1.125” (28.58 mm)
Temperature Sensing Tube Diameter:
Polycarbonate / ASA with UV Protectant | 0.86“ (21.85 mm)
Enclosure Material | Flammability Rating:
Polycarbonate / ASA with UV Protectant | UL94-V0
Enclosure Temperature Rating:
-40 to 190ºF (-40 to 88ºC)
Product Dimensions:
7.00” (177.8 mm) x 5.00” (127 mm) x 3.00” (76.2 mm)
Product Weight:
0.72 lbs. (0.33 kg)
Agency Approvals:
BTL Certified, CE, RoHS2, WEEE, China RoHS