Newly redesigned MSCT Series »

Smoke Detection Sl-2000 (Smoke Detector, Multi-Application)

This product is covered by ACI's Two (2) Year Limited Warranty. Learn more

Product overview

TEST SMOKE SL-2000 TEST PORT

Product specifications

Supply Voltage:
24 VAC/VDC, 115 VAC , 230 VAC
Maximum Operating Current (Standby):
24 VDC: 14 mA | 24 VAC: 55 mA | 115 VAC: 22 mA | 230 VAC: 12 mA
Maximum Operating Current (Alarm):
24 VDC: 68 mA | 24 VAC: 190 mA | 115 VAC: 32 mA | 230 VAC: 18 mA
Alarm Relays:
Resistive Load: 2 sets form “C” rated at 10 Amps @ 115 VAC Resistive Load: 1 set form “A” rated at 2 Amps
Trouble Relays:
Resistive Load: 1 set form “C” rated at 10 Amps @ 115 VAC
Detection Head Type:
Photoelectric or Ionization: See Ordering Grid
Air Velocity:
100 to 4,000 ft / minute
Wiring Connections / Wire Size:
Screw Terminal Blocks | Solid or Stranded: #12 to #22 AWG
Operating Temperature Range:
SL-2000-N: 32ºF to 158ºF (0ºC to 70ºC) SL-2000-P: 32ºF to 140ºF (0ºC to 60ºC)
Operating Humidity Range:
Maximum: 85 ±5 % RH (@32 ±2°C; 86 ±3.6°F) Non-Condensing / Non-Freezing
Enclosure Material:
Grey plastic backbox, clear plastic cover (Makrolon 94V-0)
NEMA Rating:
NEMA 1
Hardware Included:
7" exhaust tube, sampling tube end cap, mounting template, test magnet, & mounting hardware Note: Sampling tube not included and must be ordered.
Product Dimensions:
(L) 13.5" (342.9 mm) x (W) 4.5" (114.3 mm) x (H) 2.25" (57.15 mm)
Product Weight:
2.5 lbs (1.13 kg)
Agency Approvals:
UL & CUL Listed (UL268A, UROX, UROX7) File # S2829 CSFM Listed (3240-1004:105) MEA Accepted (73-92-E; VOL. 27)
Radioactive Element:
For SL-2000-N (Ionization) Americium 241; 0.9 Micro-Curie | Do not expose to corrosive atmospheres