This product is covered by ACI's Two (2) Year Limited Warranty. Learn more
Product overview
Multi-Voltage Control Relay, 12 to 40 VDC (20mA), Form 1C (SPDT)
Application
- Temperature Control
- Fire Alarm
- Security
- Energy Management
- Lighting Control Systems and Building Automation Systems
Product specifications
Relay Type:
Electromechanical Relay
Nominal Relay Coil Voltage (Rated Current):
PAM-1: 24 VDC (20 mA), 24 VAC (50 mA), 120 VAC (50 mA)
PAM-2: 12 VDC (20 mA), 24 VDC (20 mA)
PAM-4: 12-40 VDC (20 mA)
PAM-SD: 20-32 VDC (15 mA – 25 mA)
Contact Form:
Form 1C (SPDT Contact)
Maximum Contact Switching Voltage:
120 VAC / 24 VDC
Maximum Contact Switching Current:
PAM-1: 250 μ @ 5 VDC (PF* = 0.35) 7A @ 24 VDC (PF* = 0.35) 10A @ 120 VAC
PAM-2: 250 μ @ 5 VDC (PF* = 0.35) 7A @ 24 VDC (PF* = 0.35) 7A @ 120 VAC (PF* = 0.35)
PAM-4: 250 μ @ 5 VDC 7A @ 24 VDC 7A @ 120 VAC
PAM-SD: 250 μ @ 5 VDC (PF* = 0.35) 7A @ 24 VDC (PF* = 0.35) 7A @ 120 VAC (PF* = 0.35)
Relay Pull-In Time:
PAM-1: <1 Second (24 VDC, 24 VAC, 120 VAC)
PAM-2: <1 Second (12 / 24 VDC)
PAM-4: <1 Second (12 VDC), <3 Second (24 VDC), <1.5 Second (32 VDC)
PAM-SD: <1 Second (24-32 VDC)
Status LED Indication:
Red LED “On”: (Relay Energized “COM to N/O”) Red LED “Off”: (Relay De-Energized “Com to N/C”)
PAM-1 & PAM-2: Yes
PAM-4 & PAM-SD: No
Relay Electrical Life:
> 100,000 Cycles, typical
Relay Mechanical Life:
> 10,000,000 Cycles, typical
Lead Length | Conductor Size:
12" | 18AWG
Operating Temperature Range:
32 to 120ºF (0 to 49ºC)
Operating Humidity Range:
0 to 100%, condensing
Material Type:
Construction: 100% potted (sealed) with flying leads
Mounting:
Pre-drilled mounting screw hole and self tapping screw provided | Double sided tape provided
Agency Approvals:
UL: U0XX/7.S3403* | UL: UUKL** | MEA: 73-92-E Vol. 21 | CSFM: 7300-1004:101
Product Weight:
0.16 lbs (0.073 kg)
Product Dimensions:
(L) 1.50" (38 mm) x (W) 1.20" (31 mm) x (H) 0.77" (20 mm)