EFP Floating Pt. to Pneumatic w/ Feedback, 41 scim bleed
| Product data sheet: | |
| Product instruction: | |
| Product photo: |
Proportional pneumatic signal ranging from 0-20 psig. The pneumatic output is proportional to the signal input. The EFP* has a manual override switch with terminal strip contacts to indicate its status and a potentiometer to vary the pneumatic output. Two LEDs indicate UP or DOWN excursions, with an additional one for power indication. The EFP* offers four jumper selectable rates of change in the output pressure.
Output pressure ranges are jumper shunt selectable for 0 to 10, 0 to 15 and 0 to 20 psig, and adjustable in all ranges.
A 0-5 VDC feedback signal indicating the resultant branch line pressure, is also provided. This signal varies linearly with branch pressure range selected. EFP* is designed with electrical terminals on one end and pneumatic connections on the other, allowing for maximum convenience in wiring and tubing installation when panel mounted. Three basic configurations are available: The EFP is a constant bleed interface with branch exhaust response time determined by the bleed orifice size and pressure differentials. If power fails to the EPW, it will continue to bleed through the bleed orifice until branch pressure is zero psig.
The EFP2 incorporates two valves (one controls exhaust) and does not bleed air at set point. Its branch exhaust flow and response time are not limited by an internal restrictor and are similar to its load rate. If power fails to the EFP2, branch line pressure remains constant if the branch line does not leak air.
FAIL SAFE: The EFP2FS is a two valve fail safe model. Its 3-way branch exhaust valve allows exhaust of branch line air on a power failure.