A/TTM100-A-24'-4X

Product data sheet:
application/pdf icon
Transmitter.pdf
Product instruction:
application/pdf icon
tt.pdf
Product photo:
image
Averaging_4X.gif
Product dimensions:
A/TTM100-A-24'-4X

ACI temperature transmitters are a cost effective solution for all of your temperature measurement needs. The transmitters are accurate, durable, and reliable. Numerous mounting configurations are offered.

ACI produces two temperature transmitters, the A/TT100 for use with a 100 Ohm Platinum RTD and the A/TT1K for use with a 1K Ohm Platinum RTD. The transmitters produce a linear 4-20 mA output carried on a two-wire system. Optional output voltage ranges of (+1-5 or +2-10 VDC) can also be ordered. The transmitter is supplied factory calibrated, and supplied with zero and span potentiometers for field calibration. The transmitter is linear from -50 to 392 degrees F.

The A/TTM Series transmitters are calibrated using a high accuracy NIST traceble digital thermometer and temperature chamber at three points standard. All temperature transmitters have a five year product warranty.

The polycarbonate NEMA 4X (4X) bendable copper averaging configuration is malleable, dependable, and easy to install. The sensor can be calibrated from -58 to 392 degrees F. (Please note that the electronics are rated from -40 to 185 degrees F)

Sample Part #:

A/TTM100-6-A-12'-4X-4

Accessory Clips: (See Below)