Analog to Pressure Transducers

Product Data

ACI/PXP Series

Product Description

The ACI/PXP converts an analog input signal into a proportional pneumatic output ranging from 0 to 15 psig.  The PXP will automatically modulate, it’s control valve to control the branch line pressure to the selected setpoint as determined by the input signal. The input signal may be either a 0 to 5, 0 to 10, 0 to 15 VDC or a 4 to 20 mA signal.

Another notable feature of the PXP is that it has an adjustable, manual override potentiometer that can be used to increase or decrease the pneumatic output.  An LED is supplied for power indication.  When unlit, the LED shows that there is no power to the ACI/PXP.  All PXP’s contain a 0 to 5 VDC feedback signal that may be used to monitor the branch line pressure.

The ACI/PXP0.3 is a single valve version that has no orifice and does not bleed or exhaust air.  It depends on its branch line consuming anywhere from 14 to 73 scims.  The PXP1, 5,

and 7 are constant bleed controllers, with branch response times determined by orifice size and pressure differentials.  Both the PXP2.3 and PXP2.3FS incorporate two valves and are not constant bleed controllers.  Their branch exhaust flow and response times are similar to its load rate.

If power is lost to the PXP0.3 and PXP2.3, they will not exhaust any additional air from the branch line as long as there is no leak.  Where as the PXP1, 5, 7, and PXP2.3FS will bleed air until the branch pressure is equal to 0 psi.

 Some of the most common applications for the ACI/PXP’s are:

·         Valve and Damper Actuator Controls 
·         Compressor Staging
·         Pilot Position Control
·         Chiller Loading
·         DDC Control

 All of the units come with a two year factory warranty.  Contact ACI for more information regarding this product.

Product Specifications

Supply Voltage

Regulated 22.8 to 27.6 VDC

Supply Current

160 mA max for PXP Models

 

Regulated 21.6 to 26.4 VAC

 

200 mA max on Fail Safe Models

Supply Pressure

20 to 25 psi

Analog Input Ranges

0-5, 0-10, 0-15 VDC, or 0-20mA

Output Pressure

0 to 15 psi

Accuracy

less than or equal to +/- 3% F.S.O.

Dimensions

Ordering Information

Model # Gauge Enclosure
A/PXP [  ] [  ]  [  ]
0.3 (No Bleed) (  ) No Gauge (Std) (  ) No Enclosure (Std)
1.3 (.010" Orifice 73 scim  +/- 5%) (G) With Gauge (ENC) With Enclosure
2.3 (No Bleed 750 scims exhaust)
2.3FS (No Bleed 750 scims exhaust)
5,3  .005" Orifice (14 scims +/- 5%)
7.3  .007" Orifice (41 scims +/- 5%)

Example: A/PXP2.3-G   or A/PXP7.3  or A/PXP2.3FS-G-ENC