Differential Pressure Switches |
Product Data |
|
|
ACI/DBL Series |
|
| Product Description | ||
|
The ACI/DBL Series
Differential Pressure Switches are adjustable vacuum, pressure and
differential pressure switches designed for both HVAC and Energy
Management Applications. These
pressure switches can be used to sense either positive or differential air
pressures. These pressure
switches are compact and easy to install, since they have an internal,
linearly scaled setpoint knob with an adjustable switching differential.
These units will save installation time and money due to the ease
of the calibration and
adjustment procedures. A
manometer is not necessary but can be used to verify the overall operation
of the switches. Some of the
most common applications for the ACI/DBL Series pressure switches are:
|
The ACI/DBL Series
Pressure Switches are available in ranges from 0.08 to 0.8” w.c. all the
way up to 2.0 to 10.0” w.c.. These
units will automatically reset and have field adjustable setpoints and
switching differentials. Each
unit contains (1) SPDT contact rated for 250 VAC @ 1.5 Amps.
All wiring connections are to be made with spade connectors and a
maximum wire size of 16 AWG. The
DBL Series pressure switches contain a 1/2” conduit connection and are
mounted in a NEMA 4 transparent synthetic housing. All of the ACI/DBL
Series differential. pressure
switches come with a 2 year warranty.
Contact ACI for more information regarding the ACI/DBL Series
differential pressure switches. |
| Product Specifications | ||||||||||||||||||||
|
Dimensions

Ordering Information
| Model # | Setpoint Range | Adjustable Switching Differentiial | |||
| [ ] | [ ] | [ ] | |||
|
A/DBL |
|
*Note | The
adjustable trip setpoint within the control range is calibrated for a vertical mounting position, with the pressure ports facing downward If mounted in a horizontal position deduct 0.08" w.c. from desired setpoint for off-set adjustment. If the setpoint is at the bottom of the range, do not mount the DBL in horizontal position. |
||
|
|
205L |
-(0.08 to 0.8" w.c.) | 0.04 to 0.08" w.c. | ||
|
|
205 |
-(0.16 to 0.4" w.c.) | 0.08 to 0.16" w.c. | ||
|
|
205A |
-(0.16 to 0.8" w.c.) | 0.08 to 0.16" w.c. | ||
|
|
205B |
-(0.20 to 2.0" w.c.) | 0.08 to 0.16" w.c. | ||
|
|
205D |
-(0.80 to 4.0" w.c.) |
0.40 to 0.80" w.c. |
|
|
|
|
205E |
-(2.0 to 10.0" w.c.) |
0.60 to 1.20" w.c. |
|
|
|
|
DBZ-06 |
-(Mounting Kit.) |
2 Each (Pitots
Grommets and 6.5 feet tubing |
|
|
Example: A/DBL-205L or A/DBL-205E